I am replacing the light switch in my old home (1981). I can see that all grounds are at the back bundled together. Do I still have to legally connect the ground to the light switches' ground screw?



PS: The light on the ceiling is properly connected to the ground.



Image attached










share|improve this question



























    up vote
    2
    down vote

    favorite












    I am replacing the light switch in my old home (1981). I can see that all grounds are at the back bundled together. Do I still have to legally connect the ground to the light switches' ground screw?



    PS: The light on the ceiling is properly connected to the ground.



    Image attached










    share|improve this question























      up vote
      2
      down vote

      favorite









      up vote
      2
      down vote

      favorite











      I am replacing the light switch in my old home (1981). I can see that all grounds are at the back bundled together. Do I still have to legally connect the ground to the light switches' ground screw?



      PS: The light on the ceiling is properly connected to the ground.



      Image attached










      share|improve this question













      I am replacing the light switch in my old home (1981). I can see that all grounds are at the back bundled together. Do I still have to legally connect the ground to the light switches' ground screw?



      PS: The light on the ceiling is properly connected to the ground.



      Image attached







      switch ground






      share|improve this question













      share|improve this question











      share|improve this question




      share|improve this question










      asked 2 hours ago









      Michael

      256313




      256313




















          1 Answer
          1






          active

          oldest

          votes

















          up vote
          2
          down vote



          accepted










          Yes. Modern code requires switches to be grounded. If you are not using self grounding switches and metal boxes (and you are not), you need to run a wire from the switch ground screw to the bundle. Attaching to the end of any one of those wire will do.



          Supplement: While the electrical police are unlikely to come pounding on your door, there is a reason for code. The ground serves as a safety if the switch gets damaged. It prevents the (rare) chance of you flicking a damaged switch and getting a shock. It's worth the trouble. In general, when you do an upgrade or a fix, you bring the device or system up to code if it is possible and reasonable. In this case it is both.






          share|improve this answer






















          • Does the legal requirement apply also for old construction? I've seen many houses that do not even have wiring in the walls that has a ground.
            – Michael
            1 hour ago










          • @Michael -- since there's a ground wire there, you have to connect to it.
            – ThreePhaseEel
            59 mins ago










          • Rare? I've had it happen to me. And 1981 isn't old. Grounding came in in the 60‘s.
            – Harper
            32 mins ago










          • Will it be okay if I pull the ground from spare romex that I have and loop it around the existing bundle and then to the screw? Normally I would use the plastic screw top to merge wires together but since these are already bundled using a copper compression thingy, I wonder what would be the best way to connect the ground to the screw.
            – Michael
            27 mins ago










          • Wrapping is not likely to be sufficient. You need a wire nut or a push in connector or a crimp connector to be sure of a real bond. It looks as if the bundle has ends that could be flared a bit to accommodate. Check the electrical connections aisle of your hardware store for one that would fit. It does not need to be insulated.
            – bib
            16 mins ago










          Your Answer







          StackExchange.ready(function()
          var channelOptions =
          tags: "".split(" "),
          id: "73"
          ;
          initTagRenderer("".split(" "), "".split(" "), channelOptions);

          StackExchange.using("externalEditor", function()
          // Have to fire editor after snippets, if snippets enabled
          if (StackExchange.settings.snippets.snippetsEnabled)
          StackExchange.using("snippets", function()
          createEditor();
          );

          else
          createEditor();

          );

          function createEditor()
          StackExchange.prepareEditor(
          heartbeatType: 'answer',
          convertImagesToLinks: false,
          noModals: false,
          showLowRepImageUploadWarning: true,
          reputationToPostImages: null,
          bindNavPrevention: true,
          postfix: "",
          noCode: true, onDemand: true,
          discardSelector: ".discard-answer"
          ,immediatelyShowMarkdownHelp:true
          );



          );













           

          draft saved


          draft discarded


















          StackExchange.ready(
          function ()
          StackExchange.openid.initPostLogin('.new-post-login', 'https%3a%2f%2fdiy.stackexchange.com%2fquestions%2f149091%2fold-construction-replacing-light-switch-bundled-ground%23new-answer', 'question_page');

          );

          Post as a guest






























          1 Answer
          1






          active

          oldest

          votes








          1 Answer
          1






          active

          oldest

          votes









          active

          oldest

          votes






          active

          oldest

          votes








          up vote
          2
          down vote



          accepted










          Yes. Modern code requires switches to be grounded. If you are not using self grounding switches and metal boxes (and you are not), you need to run a wire from the switch ground screw to the bundle. Attaching to the end of any one of those wire will do.



          Supplement: While the electrical police are unlikely to come pounding on your door, there is a reason for code. The ground serves as a safety if the switch gets damaged. It prevents the (rare) chance of you flicking a damaged switch and getting a shock. It's worth the trouble. In general, when you do an upgrade or a fix, you bring the device or system up to code if it is possible and reasonable. In this case it is both.






          share|improve this answer






















          • Does the legal requirement apply also for old construction? I've seen many houses that do not even have wiring in the walls that has a ground.
            – Michael
            1 hour ago










          • @Michael -- since there's a ground wire there, you have to connect to it.
            – ThreePhaseEel
            59 mins ago










          • Rare? I've had it happen to me. And 1981 isn't old. Grounding came in in the 60‘s.
            – Harper
            32 mins ago










          • Will it be okay if I pull the ground from spare romex that I have and loop it around the existing bundle and then to the screw? Normally I would use the plastic screw top to merge wires together but since these are already bundled using a copper compression thingy, I wonder what would be the best way to connect the ground to the screw.
            – Michael
            27 mins ago










          • Wrapping is not likely to be sufficient. You need a wire nut or a push in connector or a crimp connector to be sure of a real bond. It looks as if the bundle has ends that could be flared a bit to accommodate. Check the electrical connections aisle of your hardware store for one that would fit. It does not need to be insulated.
            – bib
            16 mins ago














          up vote
          2
          down vote



          accepted










          Yes. Modern code requires switches to be grounded. If you are not using self grounding switches and metal boxes (and you are not), you need to run a wire from the switch ground screw to the bundle. Attaching to the end of any one of those wire will do.



          Supplement: While the electrical police are unlikely to come pounding on your door, there is a reason for code. The ground serves as a safety if the switch gets damaged. It prevents the (rare) chance of you flicking a damaged switch and getting a shock. It's worth the trouble. In general, when you do an upgrade or a fix, you bring the device or system up to code if it is possible and reasonable. In this case it is both.






          share|improve this answer






















          • Does the legal requirement apply also for old construction? I've seen many houses that do not even have wiring in the walls that has a ground.
            – Michael
            1 hour ago










          • @Michael -- since there's a ground wire there, you have to connect to it.
            – ThreePhaseEel
            59 mins ago










          • Rare? I've had it happen to me. And 1981 isn't old. Grounding came in in the 60‘s.
            – Harper
            32 mins ago










          • Will it be okay if I pull the ground from spare romex that I have and loop it around the existing bundle and then to the screw? Normally I would use the plastic screw top to merge wires together but since these are already bundled using a copper compression thingy, I wonder what would be the best way to connect the ground to the screw.
            – Michael
            27 mins ago










          • Wrapping is not likely to be sufficient. You need a wire nut or a push in connector or a crimp connector to be sure of a real bond. It looks as if the bundle has ends that could be flared a bit to accommodate. Check the electrical connections aisle of your hardware store for one that would fit. It does not need to be insulated.
            – bib
            16 mins ago












          up vote
          2
          down vote



          accepted







          up vote
          2
          down vote



          accepted






          Yes. Modern code requires switches to be grounded. If you are not using self grounding switches and metal boxes (and you are not), you need to run a wire from the switch ground screw to the bundle. Attaching to the end of any one of those wire will do.



          Supplement: While the electrical police are unlikely to come pounding on your door, there is a reason for code. The ground serves as a safety if the switch gets damaged. It prevents the (rare) chance of you flicking a damaged switch and getting a shock. It's worth the trouble. In general, when you do an upgrade or a fix, you bring the device or system up to code if it is possible and reasonable. In this case it is both.






          share|improve this answer














          Yes. Modern code requires switches to be grounded. If you are not using self grounding switches and metal boxes (and you are not), you need to run a wire from the switch ground screw to the bundle. Attaching to the end of any one of those wire will do.



          Supplement: While the electrical police are unlikely to come pounding on your door, there is a reason for code. The ground serves as a safety if the switch gets damaged. It prevents the (rare) chance of you flicking a damaged switch and getting a shock. It's worth the trouble. In general, when you do an upgrade or a fix, you bring the device or system up to code if it is possible and reasonable. In this case it is both.







          share|improve this answer














          share|improve this answer



          share|improve this answer








          edited 59 mins ago

























          answered 1 hour ago









          bib

          30.6k85290




          30.6k85290











          • Does the legal requirement apply also for old construction? I've seen many houses that do not even have wiring in the walls that has a ground.
            – Michael
            1 hour ago










          • @Michael -- since there's a ground wire there, you have to connect to it.
            – ThreePhaseEel
            59 mins ago










          • Rare? I've had it happen to me. And 1981 isn't old. Grounding came in in the 60‘s.
            – Harper
            32 mins ago










          • Will it be okay if I pull the ground from spare romex that I have and loop it around the existing bundle and then to the screw? Normally I would use the plastic screw top to merge wires together but since these are already bundled using a copper compression thingy, I wonder what would be the best way to connect the ground to the screw.
            – Michael
            27 mins ago










          • Wrapping is not likely to be sufficient. You need a wire nut or a push in connector or a crimp connector to be sure of a real bond. It looks as if the bundle has ends that could be flared a bit to accommodate. Check the electrical connections aisle of your hardware store for one that would fit. It does not need to be insulated.
            – bib
            16 mins ago
















          • Does the legal requirement apply also for old construction? I've seen many houses that do not even have wiring in the walls that has a ground.
            – Michael
            1 hour ago










          • @Michael -- since there's a ground wire there, you have to connect to it.
            – ThreePhaseEel
            59 mins ago










          • Rare? I've had it happen to me. And 1981 isn't old. Grounding came in in the 60‘s.
            – Harper
            32 mins ago










          • Will it be okay if I pull the ground from spare romex that I have and loop it around the existing bundle and then to the screw? Normally I would use the plastic screw top to merge wires together but since these are already bundled using a copper compression thingy, I wonder what would be the best way to connect the ground to the screw.
            – Michael
            27 mins ago










          • Wrapping is not likely to be sufficient. You need a wire nut or a push in connector or a crimp connector to be sure of a real bond. It looks as if the bundle has ends that could be flared a bit to accommodate. Check the electrical connections aisle of your hardware store for one that would fit. It does not need to be insulated.
            – bib
            16 mins ago















          Does the legal requirement apply also for old construction? I've seen many houses that do not even have wiring in the walls that has a ground.
          – Michael
          1 hour ago




          Does the legal requirement apply also for old construction? I've seen many houses that do not even have wiring in the walls that has a ground.
          – Michael
          1 hour ago












          @Michael -- since there's a ground wire there, you have to connect to it.
          – ThreePhaseEel
          59 mins ago




          @Michael -- since there's a ground wire there, you have to connect to it.
          – ThreePhaseEel
          59 mins ago












          Rare? I've had it happen to me. And 1981 isn't old. Grounding came in in the 60‘s.
          – Harper
          32 mins ago




          Rare? I've had it happen to me. And 1981 isn't old. Grounding came in in the 60‘s.
          – Harper
          32 mins ago












          Will it be okay if I pull the ground from spare romex that I have and loop it around the existing bundle and then to the screw? Normally I would use the plastic screw top to merge wires together but since these are already bundled using a copper compression thingy, I wonder what would be the best way to connect the ground to the screw.
          – Michael
          27 mins ago




          Will it be okay if I pull the ground from spare romex that I have and loop it around the existing bundle and then to the screw? Normally I would use the plastic screw top to merge wires together but since these are already bundled using a copper compression thingy, I wonder what would be the best way to connect the ground to the screw.
          – Michael
          27 mins ago












          Wrapping is not likely to be sufficient. You need a wire nut or a push in connector or a crimp connector to be sure of a real bond. It looks as if the bundle has ends that could be flared a bit to accommodate. Check the electrical connections aisle of your hardware store for one that would fit. It does not need to be insulated.
          – bib
          16 mins ago




          Wrapping is not likely to be sufficient. You need a wire nut or a push in connector or a crimp connector to be sure of a real bond. It looks as if the bundle has ends that could be flared a bit to accommodate. Check the electrical connections aisle of your hardware store for one that would fit. It does not need to be insulated.
          – bib
          16 mins ago

















           

          draft saved


          draft discarded















































           


          draft saved


          draft discarded














          StackExchange.ready(
          function ()
          StackExchange.openid.initPostLogin('.new-post-login', 'https%3a%2f%2fdiy.stackexchange.com%2fquestions%2f149091%2fold-construction-replacing-light-switch-bundled-ground%23new-answer', 'question_page');

          );

          Post as a guest













































































          Comments

          Popular posts from this blog

          Long meetings (6-7 hours a day): Being “babysat” by supervisor

          Is the Concept of Multiple Fantasy Races Scientifically Flawed? [closed]

          Confectionery