How does the strength of a square tube depend on the side size?

The name of the pictureThe name of the pictureThe name of the pictureClash Royale CLAN TAG#URR8PPP











up vote
6
down vote

favorite












There are two square tubes of the same length, material and wall thickness, one being 40x40mm, the other 20x20mm. How does their strength against bending compare?



On the one hand, the cross-sectional area of the 40mm tube is 4 times bigger. On the other hand, I guess it is mostly the two walls that are in the same plane as the bending force that work against it. The other two walls provide very little resistance comparing to the first two. And because the surface of the "working" walls of the 40mm tube is twice as much bigger as those of the 20mm one, I am inclined to think that the 40mm tube is roughly twice as much stronger. How does this conclusion stand?



More specifically, this question is about galvanized steel tubes with 1.6mm thick walls:



enter image description here



I am looking at using them as two or more horizontal beams 2.4m long which will take some evenly distributed load. The vertical space is limited so that I would rather use four/eight/sixteen 20mm tubes than two 40mm ones. But how many 20mm tubes would be roughly equal to two 40mm ones?







share|improve this question


















  • 1




    The 40x40 mm, has a bigger vertical distance to neural axis, it means more normal stress caused by bending moment. Take a look here strucalc.com/normal-stress-bending-stress-shear-stress
    – Sam Farjamirad
    Aug 9 at 8:39










  • How are the horizontal beams themselves supported... are they fixed at the ends? Resting on the ends? Supported underneath by yet more cross-members?
    – elliot svensson
    Aug 9 at 16:31










  • @elliotsvensson They rest on the ends 40mm on each side.
    – Greendrake
    Aug 9 at 23:36














up vote
6
down vote

favorite












There are two square tubes of the same length, material and wall thickness, one being 40x40mm, the other 20x20mm. How does their strength against bending compare?



On the one hand, the cross-sectional area of the 40mm tube is 4 times bigger. On the other hand, I guess it is mostly the two walls that are in the same plane as the bending force that work against it. The other two walls provide very little resistance comparing to the first two. And because the surface of the "working" walls of the 40mm tube is twice as much bigger as those of the 20mm one, I am inclined to think that the 40mm tube is roughly twice as much stronger. How does this conclusion stand?



More specifically, this question is about galvanized steel tubes with 1.6mm thick walls:



enter image description here



I am looking at using them as two or more horizontal beams 2.4m long which will take some evenly distributed load. The vertical space is limited so that I would rather use four/eight/sixteen 20mm tubes than two 40mm ones. But how many 20mm tubes would be roughly equal to two 40mm ones?







share|improve this question


















  • 1




    The 40x40 mm, has a bigger vertical distance to neural axis, it means more normal stress caused by bending moment. Take a look here strucalc.com/normal-stress-bending-stress-shear-stress
    – Sam Farjamirad
    Aug 9 at 8:39










  • How are the horizontal beams themselves supported... are they fixed at the ends? Resting on the ends? Supported underneath by yet more cross-members?
    – elliot svensson
    Aug 9 at 16:31










  • @elliotsvensson They rest on the ends 40mm on each side.
    – Greendrake
    Aug 9 at 23:36












up vote
6
down vote

favorite









up vote
6
down vote

favorite











There are two square tubes of the same length, material and wall thickness, one being 40x40mm, the other 20x20mm. How does their strength against bending compare?



On the one hand, the cross-sectional area of the 40mm tube is 4 times bigger. On the other hand, I guess it is mostly the two walls that are in the same plane as the bending force that work against it. The other two walls provide very little resistance comparing to the first two. And because the surface of the "working" walls of the 40mm tube is twice as much bigger as those of the 20mm one, I am inclined to think that the 40mm tube is roughly twice as much stronger. How does this conclusion stand?



More specifically, this question is about galvanized steel tubes with 1.6mm thick walls:



enter image description here



I am looking at using them as two or more horizontal beams 2.4m long which will take some evenly distributed load. The vertical space is limited so that I would rather use four/eight/sixteen 20mm tubes than two 40mm ones. But how many 20mm tubes would be roughly equal to two 40mm ones?







share|improve this question














There are two square tubes of the same length, material and wall thickness, one being 40x40mm, the other 20x20mm. How does their strength against bending compare?



On the one hand, the cross-sectional area of the 40mm tube is 4 times bigger. On the other hand, I guess it is mostly the two walls that are in the same plane as the bending force that work against it. The other two walls provide very little resistance comparing to the first two. And because the surface of the "working" walls of the 40mm tube is twice as much bigger as those of the 20mm one, I am inclined to think that the 40mm tube is roughly twice as much stronger. How does this conclusion stand?



More specifically, this question is about galvanized steel tubes with 1.6mm thick walls:



enter image description here



I am looking at using them as two or more horizontal beams 2.4m long which will take some evenly distributed load. The vertical space is limited so that I would rather use four/eight/sixteen 20mm tubes than two 40mm ones. But how many 20mm tubes would be roughly equal to two 40mm ones?









share|improve this question













share|improve this question




share|improve this question








edited Aug 9 at 8:36









Sam Farjamirad

440211




440211










asked Aug 9 at 8:30









Greendrake

1335




1335







  • 1




    The 40x40 mm, has a bigger vertical distance to neural axis, it means more normal stress caused by bending moment. Take a look here strucalc.com/normal-stress-bending-stress-shear-stress
    – Sam Farjamirad
    Aug 9 at 8:39










  • How are the horizontal beams themselves supported... are they fixed at the ends? Resting on the ends? Supported underneath by yet more cross-members?
    – elliot svensson
    Aug 9 at 16:31










  • @elliotsvensson They rest on the ends 40mm on each side.
    – Greendrake
    Aug 9 at 23:36












  • 1




    The 40x40 mm, has a bigger vertical distance to neural axis, it means more normal stress caused by bending moment. Take a look here strucalc.com/normal-stress-bending-stress-shear-stress
    – Sam Farjamirad
    Aug 9 at 8:39










  • How are the horizontal beams themselves supported... are they fixed at the ends? Resting on the ends? Supported underneath by yet more cross-members?
    – elliot svensson
    Aug 9 at 16:31










  • @elliotsvensson They rest on the ends 40mm on each side.
    – Greendrake
    Aug 9 at 23:36







1




1




The 40x40 mm, has a bigger vertical distance to neural axis, it means more normal stress caused by bending moment. Take a look here strucalc.com/normal-stress-bending-stress-shear-stress
– Sam Farjamirad
Aug 9 at 8:39




The 40x40 mm, has a bigger vertical distance to neural axis, it means more normal stress caused by bending moment. Take a look here strucalc.com/normal-stress-bending-stress-shear-stress
– Sam Farjamirad
Aug 9 at 8:39












How are the horizontal beams themselves supported... are they fixed at the ends? Resting on the ends? Supported underneath by yet more cross-members?
– elliot svensson
Aug 9 at 16:31




How are the horizontal beams themselves supported... are they fixed at the ends? Resting on the ends? Supported underneath by yet more cross-members?
– elliot svensson
Aug 9 at 16:31












@elliotsvensson They rest on the ends 40mm on each side.
– Greendrake
Aug 9 at 23:36




@elliotsvensson They rest on the ends 40mm on each side.
– Greendrake
Aug 9 at 23:36










3 Answers
3






active

oldest

votes

















up vote
8
down vote



accepted










Flexural capacity is based on the stress at the extreme fiber (the point farthest vertically from the neutral axis).



$$sigma = fracMyI$$



Or, rearranging



$$M = sigma fracIy = sigma S$$



M = moment capacity



$sigma$ = allowable stress



S = I/y = section modulus



So the relative capacity of the tubes will be a function of their section moduli.



For a rectangular tube:



$$S = fracBH^26 - fracbh^36H$$



rectangular tube






share|improve this answer




















  • So it turns out 40mm square tube is 4.5 times stronger than 20mm one!
    – Greendrake
    Aug 9 at 10:10






  • 2




    +1 for your beautiful diagrams. These are always a welcome sight.
    – Mark
    Aug 9 at 10:34

















up vote
2
down vote













The second moment area of a hollow square section, I, can be calculated by subtracting the I of hole from the I of square.



We call the outer side ,a and inner side b.



$$ I = frac (a^4-b^4)12 $$



And $$ S = frac (a^4-b^4)6a $$



So roughly, you need three of the smaller size beams for each 40x40 mm.



But since the deflection of the smaller beam will be THREE times more under the same load, we need to check on that not to become too excessive.



square hollow section






share|improve this answer






















  • Given that load is distributed evenly across all beams, three small beams will deflect the same as one big one, correct?
    – Greendrake
    Aug 9 at 23:41










  • Yes the deflection is the same but the support will be springy and soft. Remember when place a load p on a beam even gently, you dynamically applying three to four times the p. It is the reason soft ceilings even though structurally sound have excessive vibration under the foot traffic. The utility of a beam is to be able to support the load while it doesn't deform or vibrate much. But if we want to design a suspension system it is desirable for it to be very soft.
    – kamran
    Aug 10 at 0:30

















up vote
0
down vote













Contrary to popular opinion, the smaller tubes will provide greater strength under load than the larger tubes. Here's why:
Four 20x20mm tubes have a greater cross sectional surface area than a single 40×40mm tube. In fact, the 20×20 occupy the same external volume but have treble the strength according to the physical size. This issue is directly related to the square-cube law. Because the work of fracture required to cause structural failure in all 4 of the 20×20 tubes is higher, it is therefore more reliable. If the 4 20×20 tubes are spot welded together, their structural strength may be decreased but the rigidity of the whole resultant 40×40 tube will be 3 times stronger because of the internal cross of material measuring 3.2mm thick in the shape of a "+". Obviously the 40×40mm tube does not have that rigidity or ability to resist deflection as well as 4 20×20mm tubes welded together as a 40×40mm tube. Another advantage of the 20×20mm is their ability to resist torsion better when welded together as a box tube.






share|improve this answer




















    Your Answer




    StackExchange.ifUsing("editor", function ()
    return StackExchange.using("mathjaxEditing", function ()
    StackExchange.MarkdownEditor.creationCallbacks.add(function (editor, postfix)
    StackExchange.mathjaxEditing.prepareWmdForMathJax(editor, postfix, [["$", "$"], ["\\(","\\)"]]);
    );
    );
    , "mathjax-editing");

    StackExchange.ready(function()
    var channelOptions =
    tags: "".split(" "),
    id: "595"
    ;
    initTagRenderer("".split(" "), "".split(" "), channelOptions);

    StackExchange.using("externalEditor", function()
    // Have to fire editor after snippets, if snippets enabled
    if (StackExchange.settings.snippets.snippetsEnabled)
    StackExchange.using("snippets", function()
    createEditor();
    );

    else
    createEditor();

    );

    function createEditor()
    StackExchange.prepareEditor(
    heartbeatType: 'answer',
    convertImagesToLinks: false,
    noModals: false,
    showLowRepImageUploadWarning: true,
    reputationToPostImages: null,
    bindNavPrevention: true,
    postfix: "",
    noCode: true, onDemand: true,
    discardSelector: ".discard-answer"
    ,immediatelyShowMarkdownHelp:true
    );



    );













     

    draft saved


    draft discarded


















    StackExchange.ready(
    function ()
    StackExchange.openid.initPostLogin('.new-post-login', 'https%3a%2f%2fengineering.stackexchange.com%2fquestions%2f23135%2fhow-does-the-strength-of-a-square-tube-depend-on-the-side-size%23new-answer', 'question_page');

    );

    Post as a guest






























    3 Answers
    3






    active

    oldest

    votes








    3 Answers
    3






    active

    oldest

    votes









    active

    oldest

    votes






    active

    oldest

    votes








    up vote
    8
    down vote



    accepted










    Flexural capacity is based on the stress at the extreme fiber (the point farthest vertically from the neutral axis).



    $$sigma = fracMyI$$



    Or, rearranging



    $$M = sigma fracIy = sigma S$$



    M = moment capacity



    $sigma$ = allowable stress



    S = I/y = section modulus



    So the relative capacity of the tubes will be a function of their section moduli.



    For a rectangular tube:



    $$S = fracBH^26 - fracbh^36H$$



    rectangular tube






    share|improve this answer




















    • So it turns out 40mm square tube is 4.5 times stronger than 20mm one!
      – Greendrake
      Aug 9 at 10:10






    • 2




      +1 for your beautiful diagrams. These are always a welcome sight.
      – Mark
      Aug 9 at 10:34














    up vote
    8
    down vote



    accepted










    Flexural capacity is based on the stress at the extreme fiber (the point farthest vertically from the neutral axis).



    $$sigma = fracMyI$$



    Or, rearranging



    $$M = sigma fracIy = sigma S$$



    M = moment capacity



    $sigma$ = allowable stress



    S = I/y = section modulus



    So the relative capacity of the tubes will be a function of their section moduli.



    For a rectangular tube:



    $$S = fracBH^26 - fracbh^36H$$



    rectangular tube






    share|improve this answer




















    • So it turns out 40mm square tube is 4.5 times stronger than 20mm one!
      – Greendrake
      Aug 9 at 10:10






    • 2




      +1 for your beautiful diagrams. These are always a welcome sight.
      – Mark
      Aug 9 at 10:34












    up vote
    8
    down vote



    accepted







    up vote
    8
    down vote



    accepted






    Flexural capacity is based on the stress at the extreme fiber (the point farthest vertically from the neutral axis).



    $$sigma = fracMyI$$



    Or, rearranging



    $$M = sigma fracIy = sigma S$$



    M = moment capacity



    $sigma$ = allowable stress



    S = I/y = section modulus



    So the relative capacity of the tubes will be a function of their section moduli.



    For a rectangular tube:



    $$S = fracBH^26 - fracbh^36H$$



    rectangular tube






    share|improve this answer












    Flexural capacity is based on the stress at the extreme fiber (the point farthest vertically from the neutral axis).



    $$sigma = fracMyI$$



    Or, rearranging



    $$M = sigma fracIy = sigma S$$



    M = moment capacity



    $sigma$ = allowable stress



    S = I/y = section modulus



    So the relative capacity of the tubes will be a function of their section moduli.



    For a rectangular tube:



    $$S = fracBH^26 - fracbh^36H$$



    rectangular tube







    share|improve this answer












    share|improve this answer



    share|improve this answer










    answered Aug 9 at 9:51









    CableStay

    1,517623




    1,517623











    • So it turns out 40mm square tube is 4.5 times stronger than 20mm one!
      – Greendrake
      Aug 9 at 10:10






    • 2




      +1 for your beautiful diagrams. These are always a welcome sight.
      – Mark
      Aug 9 at 10:34
















    • So it turns out 40mm square tube is 4.5 times stronger than 20mm one!
      – Greendrake
      Aug 9 at 10:10






    • 2




      +1 for your beautiful diagrams. These are always a welcome sight.
      – Mark
      Aug 9 at 10:34















    So it turns out 40mm square tube is 4.5 times stronger than 20mm one!
    – Greendrake
    Aug 9 at 10:10




    So it turns out 40mm square tube is 4.5 times stronger than 20mm one!
    – Greendrake
    Aug 9 at 10:10




    2




    2




    +1 for your beautiful diagrams. These are always a welcome sight.
    – Mark
    Aug 9 at 10:34




    +1 for your beautiful diagrams. These are always a welcome sight.
    – Mark
    Aug 9 at 10:34










    up vote
    2
    down vote













    The second moment area of a hollow square section, I, can be calculated by subtracting the I of hole from the I of square.



    We call the outer side ,a and inner side b.



    $$ I = frac (a^4-b^4)12 $$



    And $$ S = frac (a^4-b^4)6a $$



    So roughly, you need three of the smaller size beams for each 40x40 mm.



    But since the deflection of the smaller beam will be THREE times more under the same load, we need to check on that not to become too excessive.



    square hollow section






    share|improve this answer






















    • Given that load is distributed evenly across all beams, three small beams will deflect the same as one big one, correct?
      – Greendrake
      Aug 9 at 23:41










    • Yes the deflection is the same but the support will be springy and soft. Remember when place a load p on a beam even gently, you dynamically applying three to four times the p. It is the reason soft ceilings even though structurally sound have excessive vibration under the foot traffic. The utility of a beam is to be able to support the load while it doesn't deform or vibrate much. But if we want to design a suspension system it is desirable for it to be very soft.
      – kamran
      Aug 10 at 0:30














    up vote
    2
    down vote













    The second moment area of a hollow square section, I, can be calculated by subtracting the I of hole from the I of square.



    We call the outer side ,a and inner side b.



    $$ I = frac (a^4-b^4)12 $$



    And $$ S = frac (a^4-b^4)6a $$



    So roughly, you need three of the smaller size beams for each 40x40 mm.



    But since the deflection of the smaller beam will be THREE times more under the same load, we need to check on that not to become too excessive.



    square hollow section






    share|improve this answer






















    • Given that load is distributed evenly across all beams, three small beams will deflect the same as one big one, correct?
      – Greendrake
      Aug 9 at 23:41










    • Yes the deflection is the same but the support will be springy and soft. Remember when place a load p on a beam even gently, you dynamically applying three to four times the p. It is the reason soft ceilings even though structurally sound have excessive vibration under the foot traffic. The utility of a beam is to be able to support the load while it doesn't deform or vibrate much. But if we want to design a suspension system it is desirable for it to be very soft.
      – kamran
      Aug 10 at 0:30












    up vote
    2
    down vote










    up vote
    2
    down vote









    The second moment area of a hollow square section, I, can be calculated by subtracting the I of hole from the I of square.



    We call the outer side ,a and inner side b.



    $$ I = frac (a^4-b^4)12 $$



    And $$ S = frac (a^4-b^4)6a $$



    So roughly, you need three of the smaller size beams for each 40x40 mm.



    But since the deflection of the smaller beam will be THREE times more under the same load, we need to check on that not to become too excessive.



    square hollow section






    share|improve this answer














    The second moment area of a hollow square section, I, can be calculated by subtracting the I of hole from the I of square.



    We call the outer side ,a and inner side b.



    $$ I = frac (a^4-b^4)12 $$



    And $$ S = frac (a^4-b^4)6a $$



    So roughly, you need three of the smaller size beams for each 40x40 mm.



    But since the deflection of the smaller beam will be THREE times more under the same load, we need to check on that not to become too excessive.



    square hollow section







    share|improve this answer














    share|improve this answer



    share|improve this answer








    edited Aug 9 at 14:32

























    answered Aug 9 at 14:26









    kamran

    2,4971410




    2,4971410











    • Given that load is distributed evenly across all beams, three small beams will deflect the same as one big one, correct?
      – Greendrake
      Aug 9 at 23:41










    • Yes the deflection is the same but the support will be springy and soft. Remember when place a load p on a beam even gently, you dynamically applying three to four times the p. It is the reason soft ceilings even though structurally sound have excessive vibration under the foot traffic. The utility of a beam is to be able to support the load while it doesn't deform or vibrate much. But if we want to design a suspension system it is desirable for it to be very soft.
      – kamran
      Aug 10 at 0:30
















    • Given that load is distributed evenly across all beams, three small beams will deflect the same as one big one, correct?
      – Greendrake
      Aug 9 at 23:41










    • Yes the deflection is the same but the support will be springy and soft. Remember when place a load p on a beam even gently, you dynamically applying three to four times the p. It is the reason soft ceilings even though structurally sound have excessive vibration under the foot traffic. The utility of a beam is to be able to support the load while it doesn't deform or vibrate much. But if we want to design a suspension system it is desirable for it to be very soft.
      – kamran
      Aug 10 at 0:30















    Given that load is distributed evenly across all beams, three small beams will deflect the same as one big one, correct?
    – Greendrake
    Aug 9 at 23:41




    Given that load is distributed evenly across all beams, three small beams will deflect the same as one big one, correct?
    – Greendrake
    Aug 9 at 23:41












    Yes the deflection is the same but the support will be springy and soft. Remember when place a load p on a beam even gently, you dynamically applying three to four times the p. It is the reason soft ceilings even though structurally sound have excessive vibration under the foot traffic. The utility of a beam is to be able to support the load while it doesn't deform or vibrate much. But if we want to design a suspension system it is desirable for it to be very soft.
    – kamran
    Aug 10 at 0:30




    Yes the deflection is the same but the support will be springy and soft. Remember when place a load p on a beam even gently, you dynamically applying three to four times the p. It is the reason soft ceilings even though structurally sound have excessive vibration under the foot traffic. The utility of a beam is to be able to support the load while it doesn't deform or vibrate much. But if we want to design a suspension system it is desirable for it to be very soft.
    – kamran
    Aug 10 at 0:30










    up vote
    0
    down vote













    Contrary to popular opinion, the smaller tubes will provide greater strength under load than the larger tubes. Here's why:
    Four 20x20mm tubes have a greater cross sectional surface area than a single 40×40mm tube. In fact, the 20×20 occupy the same external volume but have treble the strength according to the physical size. This issue is directly related to the square-cube law. Because the work of fracture required to cause structural failure in all 4 of the 20×20 tubes is higher, it is therefore more reliable. If the 4 20×20 tubes are spot welded together, their structural strength may be decreased but the rigidity of the whole resultant 40×40 tube will be 3 times stronger because of the internal cross of material measuring 3.2mm thick in the shape of a "+". Obviously the 40×40mm tube does not have that rigidity or ability to resist deflection as well as 4 20×20mm tubes welded together as a 40×40mm tube. Another advantage of the 20×20mm is their ability to resist torsion better when welded together as a box tube.






    share|improve this answer
























      up vote
      0
      down vote













      Contrary to popular opinion, the smaller tubes will provide greater strength under load than the larger tubes. Here's why:
      Four 20x20mm tubes have a greater cross sectional surface area than a single 40×40mm tube. In fact, the 20×20 occupy the same external volume but have treble the strength according to the physical size. This issue is directly related to the square-cube law. Because the work of fracture required to cause structural failure in all 4 of the 20×20 tubes is higher, it is therefore more reliable. If the 4 20×20 tubes are spot welded together, their structural strength may be decreased but the rigidity of the whole resultant 40×40 tube will be 3 times stronger because of the internal cross of material measuring 3.2mm thick in the shape of a "+". Obviously the 40×40mm tube does not have that rigidity or ability to resist deflection as well as 4 20×20mm tubes welded together as a 40×40mm tube. Another advantage of the 20×20mm is their ability to resist torsion better when welded together as a box tube.






      share|improve this answer






















        up vote
        0
        down vote










        up vote
        0
        down vote









        Contrary to popular opinion, the smaller tubes will provide greater strength under load than the larger tubes. Here's why:
        Four 20x20mm tubes have a greater cross sectional surface area than a single 40×40mm tube. In fact, the 20×20 occupy the same external volume but have treble the strength according to the physical size. This issue is directly related to the square-cube law. Because the work of fracture required to cause structural failure in all 4 of the 20×20 tubes is higher, it is therefore more reliable. If the 4 20×20 tubes are spot welded together, their structural strength may be decreased but the rigidity of the whole resultant 40×40 tube will be 3 times stronger because of the internal cross of material measuring 3.2mm thick in the shape of a "+". Obviously the 40×40mm tube does not have that rigidity or ability to resist deflection as well as 4 20×20mm tubes welded together as a 40×40mm tube. Another advantage of the 20×20mm is their ability to resist torsion better when welded together as a box tube.






        share|improve this answer












        Contrary to popular opinion, the smaller tubes will provide greater strength under load than the larger tubes. Here's why:
        Four 20x20mm tubes have a greater cross sectional surface area than a single 40×40mm tube. In fact, the 20×20 occupy the same external volume but have treble the strength according to the physical size. This issue is directly related to the square-cube law. Because the work of fracture required to cause structural failure in all 4 of the 20×20 tubes is higher, it is therefore more reliable. If the 4 20×20 tubes are spot welded together, their structural strength may be decreased but the rigidity of the whole resultant 40×40 tube will be 3 times stronger because of the internal cross of material measuring 3.2mm thick in the shape of a "+". Obviously the 40×40mm tube does not have that rigidity or ability to resist deflection as well as 4 20×20mm tubes welded together as a 40×40mm tube. Another advantage of the 20×20mm is their ability to resist torsion better when welded together as a box tube.







        share|improve this answer












        share|improve this answer



        share|improve this answer










        answered Aug 15 at 3:16









        Rhodie

        3049




        3049



























             

            draft saved


            draft discarded















































             


            draft saved


            draft discarded














            StackExchange.ready(
            function ()
            StackExchange.openid.initPostLogin('.new-post-login', 'https%3a%2f%2fengineering.stackexchange.com%2fquestions%2f23135%2fhow-does-the-strength-of-a-square-tube-depend-on-the-side-size%23new-answer', 'question_page');

            );

            Post as a guest













































































            Comments

            Popular posts from this blog

            What does second last employer means? [closed]

            List of Gilmore Girls characters

            One-line joke