Which wire is neutral and hot?

The name of the pictureThe name of the pictureThe name of the pictureClash Royale CLAN TAG#URR8PPP





.everyoneloves__top-leaderboard:empty,.everyoneloves__mid-leaderboard:empty margin-bottom:0;







up vote
9
down vote

favorite












I have the following wires in a box for a switch. I'm trying to replace the switch with a smart switch but cant figure out which is neutral. I thought it was the white one, but when I unbundle the white white, the light no longer turns on when I toggle the switch.



Also if I measure the voltage between the load and the box and it comes up as 120V, does that mean the missing ground wire isn't a problem?



US wiring.



enter image description here







share|improve this question


















  • 1




    If you really want to know which is hot and which neutral, you could buy a "live voltage sniffer" smile.amazon.com/gp/product/B01DFN42VG (circuit breakers have to be on for it to work). GL!
    – rogerdpack
    Aug 22 at 15:26






  • 6




    You really should have a better understanding of residential wiring before attempting work like this. There are plenty of books and online resources. Learn the basics before you start messing with your homes wiring or plumbing or anything else.
    – JPhi1618
    Aug 22 at 15:59






  • 5




    If you do not understand why an open neutral disables the circuit then stop doing electrical work until you do understand. Apparently you had an open neutral just hanging out in a box while the hot was powered; that is very dangerous. You are putting yourself, other residents, and your structure at risk.
    – Eric Lippert
    Aug 22 at 20:48










  • Please try to avoid asking two questions in one question; usually only one gets answered.
    – Eric Lippert
    Aug 22 at 20:50










  • I can only underscore what Eric Lippert has said. If you don't understand electric circuitry, then messing around with this kind of thing can void your insurance policy and get you into legal trouble. It can also cause your house to burn down, and kill you or the people you care about. Please stop this at once. Electrical work is something that should be left to the professionals.
    – Dawood ibn Kareem
    Aug 22 at 22:32
















up vote
9
down vote

favorite












I have the following wires in a box for a switch. I'm trying to replace the switch with a smart switch but cant figure out which is neutral. I thought it was the white one, but when I unbundle the white white, the light no longer turns on when I toggle the switch.



Also if I measure the voltage between the load and the box and it comes up as 120V, does that mean the missing ground wire isn't a problem?



US wiring.



enter image description here







share|improve this question


















  • 1




    If you really want to know which is hot and which neutral, you could buy a "live voltage sniffer" smile.amazon.com/gp/product/B01DFN42VG (circuit breakers have to be on for it to work). GL!
    – rogerdpack
    Aug 22 at 15:26






  • 6




    You really should have a better understanding of residential wiring before attempting work like this. There are plenty of books and online resources. Learn the basics before you start messing with your homes wiring or plumbing or anything else.
    – JPhi1618
    Aug 22 at 15:59






  • 5




    If you do not understand why an open neutral disables the circuit then stop doing electrical work until you do understand. Apparently you had an open neutral just hanging out in a box while the hot was powered; that is very dangerous. You are putting yourself, other residents, and your structure at risk.
    – Eric Lippert
    Aug 22 at 20:48










  • Please try to avoid asking two questions in one question; usually only one gets answered.
    – Eric Lippert
    Aug 22 at 20:50










  • I can only underscore what Eric Lippert has said. If you don't understand electric circuitry, then messing around with this kind of thing can void your insurance policy and get you into legal trouble. It can also cause your house to burn down, and kill you or the people you care about. Please stop this at once. Electrical work is something that should be left to the professionals.
    – Dawood ibn Kareem
    Aug 22 at 22:32












up vote
9
down vote

favorite









up vote
9
down vote

favorite











I have the following wires in a box for a switch. I'm trying to replace the switch with a smart switch but cant figure out which is neutral. I thought it was the white one, but when I unbundle the white white, the light no longer turns on when I toggle the switch.



Also if I measure the voltage between the load and the box and it comes up as 120V, does that mean the missing ground wire isn't a problem?



US wiring.



enter image description here







share|improve this question














I have the following wires in a box for a switch. I'm trying to replace the switch with a smart switch but cant figure out which is neutral. I thought it was the white one, but when I unbundle the white white, the light no longer turns on when I toggle the switch.



Also if I measure the voltage between the load and the box and it comes up as 120V, does that mean the missing ground wire isn't a problem?



US wiring.



enter image description here









share|improve this question













share|improve this question




share|improve this question








edited Sep 3 at 22:47

























asked Aug 22 at 1:01









ATG

14915




14915







  • 1




    If you really want to know which is hot and which neutral, you could buy a "live voltage sniffer" smile.amazon.com/gp/product/B01DFN42VG (circuit breakers have to be on for it to work). GL!
    – rogerdpack
    Aug 22 at 15:26






  • 6




    You really should have a better understanding of residential wiring before attempting work like this. There are plenty of books and online resources. Learn the basics before you start messing with your homes wiring or plumbing or anything else.
    – JPhi1618
    Aug 22 at 15:59






  • 5




    If you do not understand why an open neutral disables the circuit then stop doing electrical work until you do understand. Apparently you had an open neutral just hanging out in a box while the hot was powered; that is very dangerous. You are putting yourself, other residents, and your structure at risk.
    – Eric Lippert
    Aug 22 at 20:48










  • Please try to avoid asking two questions in one question; usually only one gets answered.
    – Eric Lippert
    Aug 22 at 20:50










  • I can only underscore what Eric Lippert has said. If you don't understand electric circuitry, then messing around with this kind of thing can void your insurance policy and get you into legal trouble. It can also cause your house to burn down, and kill you or the people you care about. Please stop this at once. Electrical work is something that should be left to the professionals.
    – Dawood ibn Kareem
    Aug 22 at 22:32












  • 1




    If you really want to know which is hot and which neutral, you could buy a "live voltage sniffer" smile.amazon.com/gp/product/B01DFN42VG (circuit breakers have to be on for it to work). GL!
    – rogerdpack
    Aug 22 at 15:26






  • 6




    You really should have a better understanding of residential wiring before attempting work like this. There are plenty of books and online resources. Learn the basics before you start messing with your homes wiring or plumbing or anything else.
    – JPhi1618
    Aug 22 at 15:59






  • 5




    If you do not understand why an open neutral disables the circuit then stop doing electrical work until you do understand. Apparently you had an open neutral just hanging out in a box while the hot was powered; that is very dangerous. You are putting yourself, other residents, and your structure at risk.
    – Eric Lippert
    Aug 22 at 20:48










  • Please try to avoid asking two questions in one question; usually only one gets answered.
    – Eric Lippert
    Aug 22 at 20:50










  • I can only underscore what Eric Lippert has said. If you don't understand electric circuitry, then messing around with this kind of thing can void your insurance policy and get you into legal trouble. It can also cause your house to burn down, and kill you or the people you care about. Please stop this at once. Electrical work is something that should be left to the professionals.
    – Dawood ibn Kareem
    Aug 22 at 22:32







1




1




If you really want to know which is hot and which neutral, you could buy a "live voltage sniffer" smile.amazon.com/gp/product/B01DFN42VG (circuit breakers have to be on for it to work). GL!
– rogerdpack
Aug 22 at 15:26




If you really want to know which is hot and which neutral, you could buy a "live voltage sniffer" smile.amazon.com/gp/product/B01DFN42VG (circuit breakers have to be on for it to work). GL!
– rogerdpack
Aug 22 at 15:26




6




6




You really should have a better understanding of residential wiring before attempting work like this. There are plenty of books and online resources. Learn the basics before you start messing with your homes wiring or plumbing or anything else.
– JPhi1618
Aug 22 at 15:59




You really should have a better understanding of residential wiring before attempting work like this. There are plenty of books and online resources. Learn the basics before you start messing with your homes wiring or plumbing or anything else.
– JPhi1618
Aug 22 at 15:59




5




5




If you do not understand why an open neutral disables the circuit then stop doing electrical work until you do understand. Apparently you had an open neutral just hanging out in a box while the hot was powered; that is very dangerous. You are putting yourself, other residents, and your structure at risk.
– Eric Lippert
Aug 22 at 20:48




If you do not understand why an open neutral disables the circuit then stop doing electrical work until you do understand. Apparently you had an open neutral just hanging out in a box while the hot was powered; that is very dangerous. You are putting yourself, other residents, and your structure at risk.
– Eric Lippert
Aug 22 at 20:48












Please try to avoid asking two questions in one question; usually only one gets answered.
– Eric Lippert
Aug 22 at 20:50




Please try to avoid asking two questions in one question; usually only one gets answered.
– Eric Lippert
Aug 22 at 20:50












I can only underscore what Eric Lippert has said. If you don't understand electric circuitry, then messing around with this kind of thing can void your insurance policy and get you into legal trouble. It can also cause your house to burn down, and kill you or the people you care about. Please stop this at once. Electrical work is something that should be left to the professionals.
– Dawood ibn Kareem
Aug 22 at 22:32




I can only underscore what Eric Lippert has said. If you don't understand electric circuitry, then messing around with this kind of thing can void your insurance policy and get you into legal trouble. It can also cause your house to burn down, and kill you or the people you care about. Please stop this at once. Electrical work is something that should be left to the professionals.
– Dawood ibn Kareem
Aug 22 at 22:32










5 Answers
5






active

oldest

votes

















up vote
14
down vote













You've got hot and switched hot on the existing switch. If the box is grounded properly then you will get 120V from hot (or switched hot when it is switched on) to the box. You will also get 120V from hot to neutral when the switch is off. If I understand it correctly (and Harper or one of the other real experts will correct me if I'm wrong), the circuit is actually:



hot -> switch -> switched hot -> light fixture -> neutral


The problem is often, particularly in older installations, that neutral is not present within the box because it is not needed by older switches. But neutral is needed by the light - just often that neutral will bypass the actual box since it wasn't (without a smart switch and prior to current code) required inside the box for any reason.



In your case, if I understand the pictures correctly, multiple black (hot) and white (neutral) wires nutted together. That indicates you have some additional circuits - e.g., outlets or more lights controlled by another switch - that are sharing the hot & neutral with this light switch & fixture. That is perfectly normal, but the result is that the neutral for the light fixture depends on those white wires being together. Removing the wire nut breaks the light circuit, and probably some other outlets or lights elsewhere in your house.



Bottom line: The white wires nutted together should be neutral, and you should be able to add another wire (pigtail) from the smart switch into that bundle/wire nut.



One more thing to be watch for: Hot vs. Switched Hot



In an ordinary single (i.e., one switch, as opposed to 2 switches - which is actually called 3-way) switch, it does not matter in any practical way which wire (hot vs. switched hot) is connected to which screw. However, with a smart switch you must make sure that hot and switched hot are connected according to the switch instructions. Hot is the wire that goes to the wire nutted bundle of blacks. Switched hot is the black wire (it doesn't have to be black, but it is in your particular case) going from the switch out of the box all by itself. If your switch instructions refer instead to line and load, line == hot and load == switched hot.






share|improve this answer


















  • 2




    Thanks, I think this does make sense, I didn't realize the light, or anything else needed neutral, though that makes complete sense now that you say it.
    – ATG
    Aug 22 at 1:48






  • 5




    The confusion is because "regular switches don't need neutral but smart switches need neutral" masks the fact that all circuits need neutral because in the end any properly functioning circuit (except certain 240V circuits) uses a neutral somewhere - just not necessarily in the switch box.
    – manassehkatz
    Aug 22 at 1:53

















up vote
7
down vote













Yes, there are also other cables heading off other directions to carry power onward to other loads.



The clump of all-blacks is always-hot.



The clump of all-whites is neutral.



You see where one wire on the switch is a short wire that simply goes to the always-hot clump. That style of wiring is called a "pigtail". The wire is also always-hot, and if the smart switch needs to know this, it is Line.



Disregarding green/bare ground, the 1 remaining wire on the switch is switched-hot or Load if the switch cares about that.



If the switch has more than 2 screws for (non-ground) wires, then it's a multi-way switch and life gets a lot more complicated, and the above advice would not apply.



Sometimes you see a switch with only 2 screws, but more than 1 wire going to one of the screws. This is using the switch as a splice block. In that case it's better to convert it to a pigtail, such as what you see in this box.






share|improve this answer



























    up vote
    2
    down vote













    I believe the white wires are indeed neutral. The home run hits this box, where black is switched, then continues to the light. (The other wires are other branches, maybe to other switches / lights, maybe to receptacles, etc.)



    When you disconnect the neutrals in the box, you disconnect the neutral going to the light, so it's expected that it would not light up.



    This appears to be an armored cable that uses the armor for grounding, such as type AC or MCAP, that would explain why there are no grounding conductors entering the box.



    type AC cable






    share|improve this answer


















    • 3




      @AmandeepGrewal Yes, all of this is Alternating Current (not just US, worldwide, though with differences in voltage, frequency and wiring schemes). AC here refers to Armored Cable as opposed to NM Non Metallic, or other types.
      – manassehkatz
      Aug 22 at 2:11






    • 4




      BTW Armored Cable is not the norm in US households.
      – sleblanc
      Aug 22 at 12:27






    • 1




      Have to give + I saw the insulator and metal box also and agree.+
      – Ed Beal
      Sep 3 at 23:09

















    up vote
    0
    down vote













    You've asked two questions in this question; try to avoid that. If you have two questions, ask two questions.



    Your second question was:




    if I measure the voltage between the load and the box and it comes up as 120V. Does that mean the missing ground wire isn't a problem?




    Define "problem".



    First of all: this is evidence that the box is grounded, which is good; it should be grounded. The fact that the box is grounded does not imply that all is well with the grounds. Here are some things that could be wrong in your scenario:



    The box could be grounded via an armored cable. That is not compliant with code in some areas. Why is this potentially a problem?



    • A future inspection might note that it is not to code and you might have to fix it.

    • People doing electrical work sometimes assume incorrectly that working circuits are to code, and make modifications which would be correct in a to-code circuit, and incorrect in a not-to-code circuit.

    The box could be grounded completely by accident. Perhaps it is touching a pipe that is in the same wall, and the pipe is grounded. Why is this a problem?



    • As in my previous point, you do not want to be in a situation where a future modification to the plumbing changes the grounding of the box.

    • Suppose we are in this scenario and the plumbing was never explicitly grounded to the electrical system anywhere but here. Now suppose there is a fault somewhere else that causes the plumbing to have a different ground voltage than the electrical ground. You can now be in a situation where there are two objects, both allegedly grounded, that have potential between them, which could shock a person. (This situation is common in older houses; the first modification I made to my 100 year old house was bonding the plumbing and electrical systems together so they had a common ground.)

    • Do we know that the plumbing, or whatever it is that is grounding the box by accident, actually can safely carry a fault current to ground such that the current is strong enough to trip the breaker? Maybe there is resistance; remember, conductors heat up and metal becomes less conductive when it is hot. Maybe there is a gap somewhere in the system that will spark, and ignite a mouse nest in the walls? Who knows? The emergency safety system only works by accident in this scenario.

    Is everything probably fine? Yes, it's probably fine. But that wasn't your question; your question was do we know that there are no problems with a safety system? No, we do not know that; we're guessing that there are no problems with a safety system. Absence of evidence of a problem is not evidence of absence of a problem!






    share|improve this answer




















    • Thanks, I've now called an electrician to check the ground and do the work to install the new switch. Thanks for taking he time for the detailed answer!
      – ATG
      Aug 23 at 6:57

















    up vote
    0
    down vote













    The white wires most likely are neutrals. They're nutted together because the circuit continues on to other outlets - you need to disconnect the wire nut, add a new wire, and then nut the new wire and the old wires together. Then connect that new white to the receptacle.



    Note that disconnecting the neutrals on a powered circuit that you know nothing about is a bad idea - if that was a multi-wire branch circuit, you could have sent 240v to everything on it. Be careful.






    share|improve this answer




















    • Hello, and welcome to Stack Exchange. Thanks for the answer; hope to see more from you.
      – Daniel Griscom
      Aug 23 at 2:11










    Your Answer







    StackExchange.ready(function()
    var channelOptions =
    tags: "".split(" "),
    id: "73"
    ;
    initTagRenderer("".split(" "), "".split(" "), channelOptions);

    StackExchange.using("externalEditor", function()
    // Have to fire editor after snippets, if snippets enabled
    if (StackExchange.settings.snippets.snippetsEnabled)
    StackExchange.using("snippets", function()
    createEditor();
    );

    else
    createEditor();

    );

    function createEditor()
    StackExchange.prepareEditor(
    heartbeatType: 'answer',
    convertImagesToLinks: false,
    noModals: false,
    showLowRepImageUploadWarning: true,
    reputationToPostImages: null,
    bindNavPrevention: true,
    postfix: "",
    noCode: true, onDemand: true,
    discardSelector: ".discard-answer"
    ,immediatelyShowMarkdownHelp:true
    );



    );













     

    draft saved


    draft discarded


















    StackExchange.ready(
    function ()
    StackExchange.openid.initPostLogin('.new-post-login', 'https%3a%2f%2fdiy.stackexchange.com%2fquestions%2f145588%2fwhich-wire-is-neutral-and-hot%23new-answer', 'question_page');

    );

    Post as a guest






























    5 Answers
    5






    active

    oldest

    votes








    5 Answers
    5






    active

    oldest

    votes









    active

    oldest

    votes






    active

    oldest

    votes








    up vote
    14
    down vote













    You've got hot and switched hot on the existing switch. If the box is grounded properly then you will get 120V from hot (or switched hot when it is switched on) to the box. You will also get 120V from hot to neutral when the switch is off. If I understand it correctly (and Harper or one of the other real experts will correct me if I'm wrong), the circuit is actually:



    hot -> switch -> switched hot -> light fixture -> neutral


    The problem is often, particularly in older installations, that neutral is not present within the box because it is not needed by older switches. But neutral is needed by the light - just often that neutral will bypass the actual box since it wasn't (without a smart switch and prior to current code) required inside the box for any reason.



    In your case, if I understand the pictures correctly, multiple black (hot) and white (neutral) wires nutted together. That indicates you have some additional circuits - e.g., outlets or more lights controlled by another switch - that are sharing the hot & neutral with this light switch & fixture. That is perfectly normal, but the result is that the neutral for the light fixture depends on those white wires being together. Removing the wire nut breaks the light circuit, and probably some other outlets or lights elsewhere in your house.



    Bottom line: The white wires nutted together should be neutral, and you should be able to add another wire (pigtail) from the smart switch into that bundle/wire nut.



    One more thing to be watch for: Hot vs. Switched Hot



    In an ordinary single (i.e., one switch, as opposed to 2 switches - which is actually called 3-way) switch, it does not matter in any practical way which wire (hot vs. switched hot) is connected to which screw. However, with a smart switch you must make sure that hot and switched hot are connected according to the switch instructions. Hot is the wire that goes to the wire nutted bundle of blacks. Switched hot is the black wire (it doesn't have to be black, but it is in your particular case) going from the switch out of the box all by itself. If your switch instructions refer instead to line and load, line == hot and load == switched hot.






    share|improve this answer


















    • 2




      Thanks, I think this does make sense, I didn't realize the light, or anything else needed neutral, though that makes complete sense now that you say it.
      – ATG
      Aug 22 at 1:48






    • 5




      The confusion is because "regular switches don't need neutral but smart switches need neutral" masks the fact that all circuits need neutral because in the end any properly functioning circuit (except certain 240V circuits) uses a neutral somewhere - just not necessarily in the switch box.
      – manassehkatz
      Aug 22 at 1:53














    up vote
    14
    down vote













    You've got hot and switched hot on the existing switch. If the box is grounded properly then you will get 120V from hot (or switched hot when it is switched on) to the box. You will also get 120V from hot to neutral when the switch is off. If I understand it correctly (and Harper or one of the other real experts will correct me if I'm wrong), the circuit is actually:



    hot -> switch -> switched hot -> light fixture -> neutral


    The problem is often, particularly in older installations, that neutral is not present within the box because it is not needed by older switches. But neutral is needed by the light - just often that neutral will bypass the actual box since it wasn't (without a smart switch and prior to current code) required inside the box for any reason.



    In your case, if I understand the pictures correctly, multiple black (hot) and white (neutral) wires nutted together. That indicates you have some additional circuits - e.g., outlets or more lights controlled by another switch - that are sharing the hot & neutral with this light switch & fixture. That is perfectly normal, but the result is that the neutral for the light fixture depends on those white wires being together. Removing the wire nut breaks the light circuit, and probably some other outlets or lights elsewhere in your house.



    Bottom line: The white wires nutted together should be neutral, and you should be able to add another wire (pigtail) from the smart switch into that bundle/wire nut.



    One more thing to be watch for: Hot vs. Switched Hot



    In an ordinary single (i.e., one switch, as opposed to 2 switches - which is actually called 3-way) switch, it does not matter in any practical way which wire (hot vs. switched hot) is connected to which screw. However, with a smart switch you must make sure that hot and switched hot are connected according to the switch instructions. Hot is the wire that goes to the wire nutted bundle of blacks. Switched hot is the black wire (it doesn't have to be black, but it is in your particular case) going from the switch out of the box all by itself. If your switch instructions refer instead to line and load, line == hot and load == switched hot.






    share|improve this answer


















    • 2




      Thanks, I think this does make sense, I didn't realize the light, or anything else needed neutral, though that makes complete sense now that you say it.
      – ATG
      Aug 22 at 1:48






    • 5




      The confusion is because "regular switches don't need neutral but smart switches need neutral" masks the fact that all circuits need neutral because in the end any properly functioning circuit (except certain 240V circuits) uses a neutral somewhere - just not necessarily in the switch box.
      – manassehkatz
      Aug 22 at 1:53












    up vote
    14
    down vote










    up vote
    14
    down vote









    You've got hot and switched hot on the existing switch. If the box is grounded properly then you will get 120V from hot (or switched hot when it is switched on) to the box. You will also get 120V from hot to neutral when the switch is off. If I understand it correctly (and Harper or one of the other real experts will correct me if I'm wrong), the circuit is actually:



    hot -> switch -> switched hot -> light fixture -> neutral


    The problem is often, particularly in older installations, that neutral is not present within the box because it is not needed by older switches. But neutral is needed by the light - just often that neutral will bypass the actual box since it wasn't (without a smart switch and prior to current code) required inside the box for any reason.



    In your case, if I understand the pictures correctly, multiple black (hot) and white (neutral) wires nutted together. That indicates you have some additional circuits - e.g., outlets or more lights controlled by another switch - that are sharing the hot & neutral with this light switch & fixture. That is perfectly normal, but the result is that the neutral for the light fixture depends on those white wires being together. Removing the wire nut breaks the light circuit, and probably some other outlets or lights elsewhere in your house.



    Bottom line: The white wires nutted together should be neutral, and you should be able to add another wire (pigtail) from the smart switch into that bundle/wire nut.



    One more thing to be watch for: Hot vs. Switched Hot



    In an ordinary single (i.e., one switch, as opposed to 2 switches - which is actually called 3-way) switch, it does not matter in any practical way which wire (hot vs. switched hot) is connected to which screw. However, with a smart switch you must make sure that hot and switched hot are connected according to the switch instructions. Hot is the wire that goes to the wire nutted bundle of blacks. Switched hot is the black wire (it doesn't have to be black, but it is in your particular case) going from the switch out of the box all by itself. If your switch instructions refer instead to line and load, line == hot and load == switched hot.






    share|improve this answer














    You've got hot and switched hot on the existing switch. If the box is grounded properly then you will get 120V from hot (or switched hot when it is switched on) to the box. You will also get 120V from hot to neutral when the switch is off. If I understand it correctly (and Harper or one of the other real experts will correct me if I'm wrong), the circuit is actually:



    hot -> switch -> switched hot -> light fixture -> neutral


    The problem is often, particularly in older installations, that neutral is not present within the box because it is not needed by older switches. But neutral is needed by the light - just often that neutral will bypass the actual box since it wasn't (without a smart switch and prior to current code) required inside the box for any reason.



    In your case, if I understand the pictures correctly, multiple black (hot) and white (neutral) wires nutted together. That indicates you have some additional circuits - e.g., outlets or more lights controlled by another switch - that are sharing the hot & neutral with this light switch & fixture. That is perfectly normal, but the result is that the neutral for the light fixture depends on those white wires being together. Removing the wire nut breaks the light circuit, and probably some other outlets or lights elsewhere in your house.



    Bottom line: The white wires nutted together should be neutral, and you should be able to add another wire (pigtail) from the smart switch into that bundle/wire nut.



    One more thing to be watch for: Hot vs. Switched Hot



    In an ordinary single (i.e., one switch, as opposed to 2 switches - which is actually called 3-way) switch, it does not matter in any practical way which wire (hot vs. switched hot) is connected to which screw. However, with a smart switch you must make sure that hot and switched hot are connected according to the switch instructions. Hot is the wire that goes to the wire nutted bundle of blacks. Switched hot is the black wire (it doesn't have to be black, but it is in your particular case) going from the switch out of the box all by itself. If your switch instructions refer instead to line and load, line == hot and load == switched hot.







    share|improve this answer














    share|improve this answer



    share|improve this answer








    edited Aug 22 at 13:56

























    answered Aug 22 at 1:20









    manassehkatz

    3,271419




    3,271419







    • 2




      Thanks, I think this does make sense, I didn't realize the light, or anything else needed neutral, though that makes complete sense now that you say it.
      – ATG
      Aug 22 at 1:48






    • 5




      The confusion is because "regular switches don't need neutral but smart switches need neutral" masks the fact that all circuits need neutral because in the end any properly functioning circuit (except certain 240V circuits) uses a neutral somewhere - just not necessarily in the switch box.
      – manassehkatz
      Aug 22 at 1:53












    • 2




      Thanks, I think this does make sense, I didn't realize the light, or anything else needed neutral, though that makes complete sense now that you say it.
      – ATG
      Aug 22 at 1:48






    • 5




      The confusion is because "regular switches don't need neutral but smart switches need neutral" masks the fact that all circuits need neutral because in the end any properly functioning circuit (except certain 240V circuits) uses a neutral somewhere - just not necessarily in the switch box.
      – manassehkatz
      Aug 22 at 1:53







    2




    2




    Thanks, I think this does make sense, I didn't realize the light, or anything else needed neutral, though that makes complete sense now that you say it.
    – ATG
    Aug 22 at 1:48




    Thanks, I think this does make sense, I didn't realize the light, or anything else needed neutral, though that makes complete sense now that you say it.
    – ATG
    Aug 22 at 1:48




    5




    5




    The confusion is because "regular switches don't need neutral but smart switches need neutral" masks the fact that all circuits need neutral because in the end any properly functioning circuit (except certain 240V circuits) uses a neutral somewhere - just not necessarily in the switch box.
    – manassehkatz
    Aug 22 at 1:53




    The confusion is because "regular switches don't need neutral but smart switches need neutral" masks the fact that all circuits need neutral because in the end any properly functioning circuit (except certain 240V circuits) uses a neutral somewhere - just not necessarily in the switch box.
    – manassehkatz
    Aug 22 at 1:53












    up vote
    7
    down vote













    Yes, there are also other cables heading off other directions to carry power onward to other loads.



    The clump of all-blacks is always-hot.



    The clump of all-whites is neutral.



    You see where one wire on the switch is a short wire that simply goes to the always-hot clump. That style of wiring is called a "pigtail". The wire is also always-hot, and if the smart switch needs to know this, it is Line.



    Disregarding green/bare ground, the 1 remaining wire on the switch is switched-hot or Load if the switch cares about that.



    If the switch has more than 2 screws for (non-ground) wires, then it's a multi-way switch and life gets a lot more complicated, and the above advice would not apply.



    Sometimes you see a switch with only 2 screws, but more than 1 wire going to one of the screws. This is using the switch as a splice block. In that case it's better to convert it to a pigtail, such as what you see in this box.






    share|improve this answer
























      up vote
      7
      down vote













      Yes, there are also other cables heading off other directions to carry power onward to other loads.



      The clump of all-blacks is always-hot.



      The clump of all-whites is neutral.



      You see where one wire on the switch is a short wire that simply goes to the always-hot clump. That style of wiring is called a "pigtail". The wire is also always-hot, and if the smart switch needs to know this, it is Line.



      Disregarding green/bare ground, the 1 remaining wire on the switch is switched-hot or Load if the switch cares about that.



      If the switch has more than 2 screws for (non-ground) wires, then it's a multi-way switch and life gets a lot more complicated, and the above advice would not apply.



      Sometimes you see a switch with only 2 screws, but more than 1 wire going to one of the screws. This is using the switch as a splice block. In that case it's better to convert it to a pigtail, such as what you see in this box.






      share|improve this answer






















        up vote
        7
        down vote










        up vote
        7
        down vote









        Yes, there are also other cables heading off other directions to carry power onward to other loads.



        The clump of all-blacks is always-hot.



        The clump of all-whites is neutral.



        You see where one wire on the switch is a short wire that simply goes to the always-hot clump. That style of wiring is called a "pigtail". The wire is also always-hot, and if the smart switch needs to know this, it is Line.



        Disregarding green/bare ground, the 1 remaining wire on the switch is switched-hot or Load if the switch cares about that.



        If the switch has more than 2 screws for (non-ground) wires, then it's a multi-way switch and life gets a lot more complicated, and the above advice would not apply.



        Sometimes you see a switch with only 2 screws, but more than 1 wire going to one of the screws. This is using the switch as a splice block. In that case it's better to convert it to a pigtail, such as what you see in this box.






        share|improve this answer












        Yes, there are also other cables heading off other directions to carry power onward to other loads.



        The clump of all-blacks is always-hot.



        The clump of all-whites is neutral.



        You see where one wire on the switch is a short wire that simply goes to the always-hot clump. That style of wiring is called a "pigtail". The wire is also always-hot, and if the smart switch needs to know this, it is Line.



        Disregarding green/bare ground, the 1 remaining wire on the switch is switched-hot or Load if the switch cares about that.



        If the switch has more than 2 screws for (non-ground) wires, then it's a multi-way switch and life gets a lot more complicated, and the above advice would not apply.



        Sometimes you see a switch with only 2 screws, but more than 1 wire going to one of the screws. This is using the switch as a splice block. In that case it's better to convert it to a pigtail, such as what you see in this box.







        share|improve this answer












        share|improve this answer



        share|improve this answer










        answered Aug 22 at 5:13









        Harper

        54.9k332112




        54.9k332112




















            up vote
            2
            down vote













            I believe the white wires are indeed neutral. The home run hits this box, where black is switched, then continues to the light. (The other wires are other branches, maybe to other switches / lights, maybe to receptacles, etc.)



            When you disconnect the neutrals in the box, you disconnect the neutral going to the light, so it's expected that it would not light up.



            This appears to be an armored cable that uses the armor for grounding, such as type AC or MCAP, that would explain why there are no grounding conductors entering the box.



            type AC cable






            share|improve this answer


















            • 3




              @AmandeepGrewal Yes, all of this is Alternating Current (not just US, worldwide, though with differences in voltage, frequency and wiring schemes). AC here refers to Armored Cable as opposed to NM Non Metallic, or other types.
              – manassehkatz
              Aug 22 at 2:11






            • 4




              BTW Armored Cable is not the norm in US households.
              – sleblanc
              Aug 22 at 12:27






            • 1




              Have to give + I saw the insulator and metal box also and agree.+
              – Ed Beal
              Sep 3 at 23:09














            up vote
            2
            down vote













            I believe the white wires are indeed neutral. The home run hits this box, where black is switched, then continues to the light. (The other wires are other branches, maybe to other switches / lights, maybe to receptacles, etc.)



            When you disconnect the neutrals in the box, you disconnect the neutral going to the light, so it's expected that it would not light up.



            This appears to be an armored cable that uses the armor for grounding, such as type AC or MCAP, that would explain why there are no grounding conductors entering the box.



            type AC cable






            share|improve this answer


















            • 3




              @AmandeepGrewal Yes, all of this is Alternating Current (not just US, worldwide, though with differences in voltage, frequency and wiring schemes). AC here refers to Armored Cable as opposed to NM Non Metallic, or other types.
              – manassehkatz
              Aug 22 at 2:11






            • 4




              BTW Armored Cable is not the norm in US households.
              – sleblanc
              Aug 22 at 12:27






            • 1




              Have to give + I saw the insulator and metal box also and agree.+
              – Ed Beal
              Sep 3 at 23:09












            up vote
            2
            down vote










            up vote
            2
            down vote









            I believe the white wires are indeed neutral. The home run hits this box, where black is switched, then continues to the light. (The other wires are other branches, maybe to other switches / lights, maybe to receptacles, etc.)



            When you disconnect the neutrals in the box, you disconnect the neutral going to the light, so it's expected that it would not light up.



            This appears to be an armored cable that uses the armor for grounding, such as type AC or MCAP, that would explain why there are no grounding conductors entering the box.



            type AC cable






            share|improve this answer














            I believe the white wires are indeed neutral. The home run hits this box, where black is switched, then continues to the light. (The other wires are other branches, maybe to other switches / lights, maybe to receptacles, etc.)



            When you disconnect the neutrals in the box, you disconnect the neutral going to the light, so it's expected that it would not light up.



            This appears to be an armored cable that uses the armor for grounding, such as type AC or MCAP, that would explain why there are no grounding conductors entering the box.



            type AC cable







            share|improve this answer














            share|improve this answer



            share|improve this answer








            edited Aug 22 at 10:23

























            answered Aug 22 at 1:25









            batsplatsterson

            5,064920




            5,064920







            • 3




              @AmandeepGrewal Yes, all of this is Alternating Current (not just US, worldwide, though with differences in voltage, frequency and wiring schemes). AC here refers to Armored Cable as opposed to NM Non Metallic, or other types.
              – manassehkatz
              Aug 22 at 2:11






            • 4




              BTW Armored Cable is not the norm in US households.
              – sleblanc
              Aug 22 at 12:27






            • 1




              Have to give + I saw the insulator and metal box also and agree.+
              – Ed Beal
              Sep 3 at 23:09












            • 3




              @AmandeepGrewal Yes, all of this is Alternating Current (not just US, worldwide, though with differences in voltage, frequency and wiring schemes). AC here refers to Armored Cable as opposed to NM Non Metallic, or other types.
              – manassehkatz
              Aug 22 at 2:11






            • 4




              BTW Armored Cable is not the norm in US households.
              – sleblanc
              Aug 22 at 12:27






            • 1




              Have to give + I saw the insulator and metal box also and agree.+
              – Ed Beal
              Sep 3 at 23:09







            3




            3




            @AmandeepGrewal Yes, all of this is Alternating Current (not just US, worldwide, though with differences in voltage, frequency and wiring schemes). AC here refers to Armored Cable as opposed to NM Non Metallic, or other types.
            – manassehkatz
            Aug 22 at 2:11




            @AmandeepGrewal Yes, all of this is Alternating Current (not just US, worldwide, though with differences in voltage, frequency and wiring schemes). AC here refers to Armored Cable as opposed to NM Non Metallic, or other types.
            – manassehkatz
            Aug 22 at 2:11




            4




            4




            BTW Armored Cable is not the norm in US households.
            – sleblanc
            Aug 22 at 12:27




            BTW Armored Cable is not the norm in US households.
            – sleblanc
            Aug 22 at 12:27




            1




            1




            Have to give + I saw the insulator and metal box also and agree.+
            – Ed Beal
            Sep 3 at 23:09




            Have to give + I saw the insulator and metal box also and agree.+
            – Ed Beal
            Sep 3 at 23:09










            up vote
            0
            down vote













            You've asked two questions in this question; try to avoid that. If you have two questions, ask two questions.



            Your second question was:




            if I measure the voltage between the load and the box and it comes up as 120V. Does that mean the missing ground wire isn't a problem?




            Define "problem".



            First of all: this is evidence that the box is grounded, which is good; it should be grounded. The fact that the box is grounded does not imply that all is well with the grounds. Here are some things that could be wrong in your scenario:



            The box could be grounded via an armored cable. That is not compliant with code in some areas. Why is this potentially a problem?



            • A future inspection might note that it is not to code and you might have to fix it.

            • People doing electrical work sometimes assume incorrectly that working circuits are to code, and make modifications which would be correct in a to-code circuit, and incorrect in a not-to-code circuit.

            The box could be grounded completely by accident. Perhaps it is touching a pipe that is in the same wall, and the pipe is grounded. Why is this a problem?



            • As in my previous point, you do not want to be in a situation where a future modification to the plumbing changes the grounding of the box.

            • Suppose we are in this scenario and the plumbing was never explicitly grounded to the electrical system anywhere but here. Now suppose there is a fault somewhere else that causes the plumbing to have a different ground voltage than the electrical ground. You can now be in a situation where there are two objects, both allegedly grounded, that have potential between them, which could shock a person. (This situation is common in older houses; the first modification I made to my 100 year old house was bonding the plumbing and electrical systems together so they had a common ground.)

            • Do we know that the plumbing, or whatever it is that is grounding the box by accident, actually can safely carry a fault current to ground such that the current is strong enough to trip the breaker? Maybe there is resistance; remember, conductors heat up and metal becomes less conductive when it is hot. Maybe there is a gap somewhere in the system that will spark, and ignite a mouse nest in the walls? Who knows? The emergency safety system only works by accident in this scenario.

            Is everything probably fine? Yes, it's probably fine. But that wasn't your question; your question was do we know that there are no problems with a safety system? No, we do not know that; we're guessing that there are no problems with a safety system. Absence of evidence of a problem is not evidence of absence of a problem!






            share|improve this answer




















            • Thanks, I've now called an electrician to check the ground and do the work to install the new switch. Thanks for taking he time for the detailed answer!
              – ATG
              Aug 23 at 6:57














            up vote
            0
            down vote













            You've asked two questions in this question; try to avoid that. If you have two questions, ask two questions.



            Your second question was:




            if I measure the voltage between the load and the box and it comes up as 120V. Does that mean the missing ground wire isn't a problem?




            Define "problem".



            First of all: this is evidence that the box is grounded, which is good; it should be grounded. The fact that the box is grounded does not imply that all is well with the grounds. Here are some things that could be wrong in your scenario:



            The box could be grounded via an armored cable. That is not compliant with code in some areas. Why is this potentially a problem?



            • A future inspection might note that it is not to code and you might have to fix it.

            • People doing electrical work sometimes assume incorrectly that working circuits are to code, and make modifications which would be correct in a to-code circuit, and incorrect in a not-to-code circuit.

            The box could be grounded completely by accident. Perhaps it is touching a pipe that is in the same wall, and the pipe is grounded. Why is this a problem?



            • As in my previous point, you do not want to be in a situation where a future modification to the plumbing changes the grounding of the box.

            • Suppose we are in this scenario and the plumbing was never explicitly grounded to the electrical system anywhere but here. Now suppose there is a fault somewhere else that causes the plumbing to have a different ground voltage than the electrical ground. You can now be in a situation where there are two objects, both allegedly grounded, that have potential between them, which could shock a person. (This situation is common in older houses; the first modification I made to my 100 year old house was bonding the plumbing and electrical systems together so they had a common ground.)

            • Do we know that the plumbing, or whatever it is that is grounding the box by accident, actually can safely carry a fault current to ground such that the current is strong enough to trip the breaker? Maybe there is resistance; remember, conductors heat up and metal becomes less conductive when it is hot. Maybe there is a gap somewhere in the system that will spark, and ignite a mouse nest in the walls? Who knows? The emergency safety system only works by accident in this scenario.

            Is everything probably fine? Yes, it's probably fine. But that wasn't your question; your question was do we know that there are no problems with a safety system? No, we do not know that; we're guessing that there are no problems with a safety system. Absence of evidence of a problem is not evidence of absence of a problem!






            share|improve this answer




















            • Thanks, I've now called an electrician to check the ground and do the work to install the new switch. Thanks for taking he time for the detailed answer!
              – ATG
              Aug 23 at 6:57












            up vote
            0
            down vote










            up vote
            0
            down vote









            You've asked two questions in this question; try to avoid that. If you have two questions, ask two questions.



            Your second question was:




            if I measure the voltage between the load and the box and it comes up as 120V. Does that mean the missing ground wire isn't a problem?




            Define "problem".



            First of all: this is evidence that the box is grounded, which is good; it should be grounded. The fact that the box is grounded does not imply that all is well with the grounds. Here are some things that could be wrong in your scenario:



            The box could be grounded via an armored cable. That is not compliant with code in some areas. Why is this potentially a problem?



            • A future inspection might note that it is not to code and you might have to fix it.

            • People doing electrical work sometimes assume incorrectly that working circuits are to code, and make modifications which would be correct in a to-code circuit, and incorrect in a not-to-code circuit.

            The box could be grounded completely by accident. Perhaps it is touching a pipe that is in the same wall, and the pipe is grounded. Why is this a problem?



            • As in my previous point, you do not want to be in a situation where a future modification to the plumbing changes the grounding of the box.

            • Suppose we are in this scenario and the plumbing was never explicitly grounded to the electrical system anywhere but here. Now suppose there is a fault somewhere else that causes the plumbing to have a different ground voltage than the electrical ground. You can now be in a situation where there are two objects, both allegedly grounded, that have potential between them, which could shock a person. (This situation is common in older houses; the first modification I made to my 100 year old house was bonding the plumbing and electrical systems together so they had a common ground.)

            • Do we know that the plumbing, or whatever it is that is grounding the box by accident, actually can safely carry a fault current to ground such that the current is strong enough to trip the breaker? Maybe there is resistance; remember, conductors heat up and metal becomes less conductive when it is hot. Maybe there is a gap somewhere in the system that will spark, and ignite a mouse nest in the walls? Who knows? The emergency safety system only works by accident in this scenario.

            Is everything probably fine? Yes, it's probably fine. But that wasn't your question; your question was do we know that there are no problems with a safety system? No, we do not know that; we're guessing that there are no problems with a safety system. Absence of evidence of a problem is not evidence of absence of a problem!






            share|improve this answer












            You've asked two questions in this question; try to avoid that. If you have two questions, ask two questions.



            Your second question was:




            if I measure the voltage between the load and the box and it comes up as 120V. Does that mean the missing ground wire isn't a problem?




            Define "problem".



            First of all: this is evidence that the box is grounded, which is good; it should be grounded. The fact that the box is grounded does not imply that all is well with the grounds. Here are some things that could be wrong in your scenario:



            The box could be grounded via an armored cable. That is not compliant with code in some areas. Why is this potentially a problem?



            • A future inspection might note that it is not to code and you might have to fix it.

            • People doing electrical work sometimes assume incorrectly that working circuits are to code, and make modifications which would be correct in a to-code circuit, and incorrect in a not-to-code circuit.

            The box could be grounded completely by accident. Perhaps it is touching a pipe that is in the same wall, and the pipe is grounded. Why is this a problem?



            • As in my previous point, you do not want to be in a situation where a future modification to the plumbing changes the grounding of the box.

            • Suppose we are in this scenario and the plumbing was never explicitly grounded to the electrical system anywhere but here. Now suppose there is a fault somewhere else that causes the plumbing to have a different ground voltage than the electrical ground. You can now be in a situation where there are two objects, both allegedly grounded, that have potential between them, which could shock a person. (This situation is common in older houses; the first modification I made to my 100 year old house was bonding the plumbing and electrical systems together so they had a common ground.)

            • Do we know that the plumbing, or whatever it is that is grounding the box by accident, actually can safely carry a fault current to ground such that the current is strong enough to trip the breaker? Maybe there is resistance; remember, conductors heat up and metal becomes less conductive when it is hot. Maybe there is a gap somewhere in the system that will spark, and ignite a mouse nest in the walls? Who knows? The emergency safety system only works by accident in this scenario.

            Is everything probably fine? Yes, it's probably fine. But that wasn't your question; your question was do we know that there are no problems with a safety system? No, we do not know that; we're guessing that there are no problems with a safety system. Absence of evidence of a problem is not evidence of absence of a problem!







            share|improve this answer












            share|improve this answer



            share|improve this answer










            answered Aug 22 at 21:01









            Eric Lippert

            877711




            877711











            • Thanks, I've now called an electrician to check the ground and do the work to install the new switch. Thanks for taking he time for the detailed answer!
              – ATG
              Aug 23 at 6:57
















            • Thanks, I've now called an electrician to check the ground and do the work to install the new switch. Thanks for taking he time for the detailed answer!
              – ATG
              Aug 23 at 6:57















            Thanks, I've now called an electrician to check the ground and do the work to install the new switch. Thanks for taking he time for the detailed answer!
            – ATG
            Aug 23 at 6:57




            Thanks, I've now called an electrician to check the ground and do the work to install the new switch. Thanks for taking he time for the detailed answer!
            – ATG
            Aug 23 at 6:57










            up vote
            0
            down vote













            The white wires most likely are neutrals. They're nutted together because the circuit continues on to other outlets - you need to disconnect the wire nut, add a new wire, and then nut the new wire and the old wires together. Then connect that new white to the receptacle.



            Note that disconnecting the neutrals on a powered circuit that you know nothing about is a bad idea - if that was a multi-wire branch circuit, you could have sent 240v to everything on it. Be careful.






            share|improve this answer




















            • Hello, and welcome to Stack Exchange. Thanks for the answer; hope to see more from you.
              – Daniel Griscom
              Aug 23 at 2:11














            up vote
            0
            down vote













            The white wires most likely are neutrals. They're nutted together because the circuit continues on to other outlets - you need to disconnect the wire nut, add a new wire, and then nut the new wire and the old wires together. Then connect that new white to the receptacle.



            Note that disconnecting the neutrals on a powered circuit that you know nothing about is a bad idea - if that was a multi-wire branch circuit, you could have sent 240v to everything on it. Be careful.






            share|improve this answer




















            • Hello, and welcome to Stack Exchange. Thanks for the answer; hope to see more from you.
              – Daniel Griscom
              Aug 23 at 2:11












            up vote
            0
            down vote










            up vote
            0
            down vote









            The white wires most likely are neutrals. They're nutted together because the circuit continues on to other outlets - you need to disconnect the wire nut, add a new wire, and then nut the new wire and the old wires together. Then connect that new white to the receptacle.



            Note that disconnecting the neutrals on a powered circuit that you know nothing about is a bad idea - if that was a multi-wire branch circuit, you could have sent 240v to everything on it. Be careful.






            share|improve this answer












            The white wires most likely are neutrals. They're nutted together because the circuit continues on to other outlets - you need to disconnect the wire nut, add a new wire, and then nut the new wire and the old wires together. Then connect that new white to the receptacle.



            Note that disconnecting the neutrals on a powered circuit that you know nothing about is a bad idea - if that was a multi-wire branch circuit, you could have sent 240v to everything on it. Be careful.







            share|improve this answer












            share|improve this answer



            share|improve this answer










            answered Aug 23 at 1:22









            Mike B

            1




            1











            • Hello, and welcome to Stack Exchange. Thanks for the answer; hope to see more from you.
              – Daniel Griscom
              Aug 23 at 2:11
















            • Hello, and welcome to Stack Exchange. Thanks for the answer; hope to see more from you.
              – Daniel Griscom
              Aug 23 at 2:11















            Hello, and welcome to Stack Exchange. Thanks for the answer; hope to see more from you.
            – Daniel Griscom
            Aug 23 at 2:11




            Hello, and welcome to Stack Exchange. Thanks for the answer; hope to see more from you.
            – Daniel Griscom
            Aug 23 at 2:11

















             

            draft saved


            draft discarded















































             


            draft saved


            draft discarded














            StackExchange.ready(
            function ()
            StackExchange.openid.initPostLogin('.new-post-login', 'https%3a%2f%2fdiy.stackexchange.com%2fquestions%2f145588%2fwhich-wire-is-neutral-and-hot%23new-answer', 'question_page');

            );

            Post as a guest













































































            Comments

            Popular posts from this blog

            What does second last employer means? [closed]

            List of Gilmore Girls characters

            One-line joke