What are the pros and cons of having your own UPS attached to your own server hosted in a data center?

The name of the pictureThe name of the pictureThe name of the pictureClash Royale CLAN TAG#URR8PPP











up vote
47
down vote

favorite
3












According to this comment by Tom O'Connor (slightly edited below):




You can seriously tick off a datacentre by putting an UPS inside your own rack.




What are the risks to the data center should a customer (somehow) choose to do this?







share|improve this question


















  • 7




    Things don't happen in a vacuum. If your datacenter prohibits the use of a rack UPS then they'll either prevent you from installing one in the first place or they'll require you to remove it.
    – joeqwerty
    Aug 27 at 14:09






  • 3




    Yes, I certainly have no intention of doing this myself. Not knowing many of the edge details regarding server setups, I was simply curious as to why someone would think this was a good idea, and what risk this could pose to a data center.
    – JonathanDavidArndt
    Aug 27 at 14:43










  • I don't have the maths for this, but there is a thing called Power Factor, where the characteristics of the load affect the supply. A UPS has a different power factor than the load. en.wikipedia.org/wiki/Power_factor Someone with better skills can do a proper answer.
    – Criggie
    Aug 28 at 2:14






  • 2




    Not all datacenters are created equal. Not all datacenters will have the same rules regarding the use of a UPS inside your cage. I've worked in datacenters where all the points given by others in this thread are valid and a UPS should never be used. I've also worked in lower-budget datacenters with less reliable power than rural Afghanistan and the UPS was welcome and useful.
    – Ryan Ries
    Aug 28 at 13:53











  • Sometimes you can request unconditioned generator power. I used to have some equipment in a coloc with a kinetic backup power system (i.e. a flywheel) that would power the datacenter just long enough for the generator to start (20 seconds? "If the generator doesn't start by then it's not going to start at all"). One large customer didn't trust that system, so they had their own large UPS setup in their cage (which was connected to the facility EPO button). I was in that coloc for 2 years, and it survived several power failures without issue so I don't know if the concerns were warranted.
    – Johnny
    Aug 29 at 20:17














up vote
47
down vote

favorite
3












According to this comment by Tom O'Connor (slightly edited below):




You can seriously tick off a datacentre by putting an UPS inside your own rack.




What are the risks to the data center should a customer (somehow) choose to do this?







share|improve this question


















  • 7




    Things don't happen in a vacuum. If your datacenter prohibits the use of a rack UPS then they'll either prevent you from installing one in the first place or they'll require you to remove it.
    – joeqwerty
    Aug 27 at 14:09






  • 3




    Yes, I certainly have no intention of doing this myself. Not knowing many of the edge details regarding server setups, I was simply curious as to why someone would think this was a good idea, and what risk this could pose to a data center.
    – JonathanDavidArndt
    Aug 27 at 14:43










  • I don't have the maths for this, but there is a thing called Power Factor, where the characteristics of the load affect the supply. A UPS has a different power factor than the load. en.wikipedia.org/wiki/Power_factor Someone with better skills can do a proper answer.
    – Criggie
    Aug 28 at 2:14






  • 2




    Not all datacenters are created equal. Not all datacenters will have the same rules regarding the use of a UPS inside your cage. I've worked in datacenters where all the points given by others in this thread are valid and a UPS should never be used. I've also worked in lower-budget datacenters with less reliable power than rural Afghanistan and the UPS was welcome and useful.
    – Ryan Ries
    Aug 28 at 13:53











  • Sometimes you can request unconditioned generator power. I used to have some equipment in a coloc with a kinetic backup power system (i.e. a flywheel) that would power the datacenter just long enough for the generator to start (20 seconds? "If the generator doesn't start by then it's not going to start at all"). One large customer didn't trust that system, so they had their own large UPS setup in their cage (which was connected to the facility EPO button). I was in that coloc for 2 years, and it survived several power failures without issue so I don't know if the concerns were warranted.
    – Johnny
    Aug 29 at 20:17












up vote
47
down vote

favorite
3









up vote
47
down vote

favorite
3






3





According to this comment by Tom O'Connor (slightly edited below):




You can seriously tick off a datacentre by putting an UPS inside your own rack.




What are the risks to the data center should a customer (somehow) choose to do this?







share|improve this question














According to this comment by Tom O'Connor (slightly edited below):




You can seriously tick off a datacentre by putting an UPS inside your own rack.




What are the risks to the data center should a customer (somehow) choose to do this?









share|improve this question













share|improve this question




share|improve this question








edited Aug 29 at 16:49

























asked Aug 27 at 13:26









JonathanDavidArndt

1,01911424




1,01911424







  • 7




    Things don't happen in a vacuum. If your datacenter prohibits the use of a rack UPS then they'll either prevent you from installing one in the first place or they'll require you to remove it.
    – joeqwerty
    Aug 27 at 14:09






  • 3




    Yes, I certainly have no intention of doing this myself. Not knowing many of the edge details regarding server setups, I was simply curious as to why someone would think this was a good idea, and what risk this could pose to a data center.
    – JonathanDavidArndt
    Aug 27 at 14:43










  • I don't have the maths for this, but there is a thing called Power Factor, where the characteristics of the load affect the supply. A UPS has a different power factor than the load. en.wikipedia.org/wiki/Power_factor Someone with better skills can do a proper answer.
    – Criggie
    Aug 28 at 2:14






  • 2




    Not all datacenters are created equal. Not all datacenters will have the same rules regarding the use of a UPS inside your cage. I've worked in datacenters where all the points given by others in this thread are valid and a UPS should never be used. I've also worked in lower-budget datacenters with less reliable power than rural Afghanistan and the UPS was welcome and useful.
    – Ryan Ries
    Aug 28 at 13:53











  • Sometimes you can request unconditioned generator power. I used to have some equipment in a coloc with a kinetic backup power system (i.e. a flywheel) that would power the datacenter just long enough for the generator to start (20 seconds? "If the generator doesn't start by then it's not going to start at all"). One large customer didn't trust that system, so they had their own large UPS setup in their cage (which was connected to the facility EPO button). I was in that coloc for 2 years, and it survived several power failures without issue so I don't know if the concerns were warranted.
    – Johnny
    Aug 29 at 20:17












  • 7




    Things don't happen in a vacuum. If your datacenter prohibits the use of a rack UPS then they'll either prevent you from installing one in the first place or they'll require you to remove it.
    – joeqwerty
    Aug 27 at 14:09






  • 3




    Yes, I certainly have no intention of doing this myself. Not knowing many of the edge details regarding server setups, I was simply curious as to why someone would think this was a good idea, and what risk this could pose to a data center.
    – JonathanDavidArndt
    Aug 27 at 14:43










  • I don't have the maths for this, but there is a thing called Power Factor, where the characteristics of the load affect the supply. A UPS has a different power factor than the load. en.wikipedia.org/wiki/Power_factor Someone with better skills can do a proper answer.
    – Criggie
    Aug 28 at 2:14






  • 2




    Not all datacenters are created equal. Not all datacenters will have the same rules regarding the use of a UPS inside your cage. I've worked in datacenters where all the points given by others in this thread are valid and a UPS should never be used. I've also worked in lower-budget datacenters with less reliable power than rural Afghanistan and the UPS was welcome and useful.
    – Ryan Ries
    Aug 28 at 13:53











  • Sometimes you can request unconditioned generator power. I used to have some equipment in a coloc with a kinetic backup power system (i.e. a flywheel) that would power the datacenter just long enough for the generator to start (20 seconds? "If the generator doesn't start by then it's not going to start at all"). One large customer didn't trust that system, so they had their own large UPS setup in their cage (which was connected to the facility EPO button). I was in that coloc for 2 years, and it survived several power failures without issue so I don't know if the concerns were warranted.
    – Johnny
    Aug 29 at 20:17







7




7




Things don't happen in a vacuum. If your datacenter prohibits the use of a rack UPS then they'll either prevent you from installing one in the first place or they'll require you to remove it.
– joeqwerty
Aug 27 at 14:09




Things don't happen in a vacuum. If your datacenter prohibits the use of a rack UPS then they'll either prevent you from installing one in the first place or they'll require you to remove it.
– joeqwerty
Aug 27 at 14:09




3




3




Yes, I certainly have no intention of doing this myself. Not knowing many of the edge details regarding server setups, I was simply curious as to why someone would think this was a good idea, and what risk this could pose to a data center.
– JonathanDavidArndt
Aug 27 at 14:43




Yes, I certainly have no intention of doing this myself. Not knowing many of the edge details regarding server setups, I was simply curious as to why someone would think this was a good idea, and what risk this could pose to a data center.
– JonathanDavidArndt
Aug 27 at 14:43












I don't have the maths for this, but there is a thing called Power Factor, where the characteristics of the load affect the supply. A UPS has a different power factor than the load. en.wikipedia.org/wiki/Power_factor Someone with better skills can do a proper answer.
– Criggie
Aug 28 at 2:14




I don't have the maths for this, but there is a thing called Power Factor, where the characteristics of the load affect the supply. A UPS has a different power factor than the load. en.wikipedia.org/wiki/Power_factor Someone with better skills can do a proper answer.
– Criggie
Aug 28 at 2:14




2




2




Not all datacenters are created equal. Not all datacenters will have the same rules regarding the use of a UPS inside your cage. I've worked in datacenters where all the points given by others in this thread are valid and a UPS should never be used. I've also worked in lower-budget datacenters with less reliable power than rural Afghanistan and the UPS was welcome and useful.
– Ryan Ries
Aug 28 at 13:53





Not all datacenters are created equal. Not all datacenters will have the same rules regarding the use of a UPS inside your cage. I've worked in datacenters where all the points given by others in this thread are valid and a UPS should never be used. I've also worked in lower-budget datacenters with less reliable power than rural Afghanistan and the UPS was welcome and useful.
– Ryan Ries
Aug 28 at 13:53













Sometimes you can request unconditioned generator power. I used to have some equipment in a coloc with a kinetic backup power system (i.e. a flywheel) that would power the datacenter just long enough for the generator to start (20 seconds? "If the generator doesn't start by then it's not going to start at all"). One large customer didn't trust that system, so they had their own large UPS setup in their cage (which was connected to the facility EPO button). I was in that coloc for 2 years, and it survived several power failures without issue so I don't know if the concerns were warranted.
– Johnny
Aug 29 at 20:17




Sometimes you can request unconditioned generator power. I used to have some equipment in a coloc with a kinetic backup power system (i.e. a flywheel) that would power the datacenter just long enough for the generator to start (20 seconds? "If the generator doesn't start by then it's not going to start at all"). One large customer didn't trust that system, so they had their own large UPS setup in their cage (which was connected to the facility EPO button). I was in that coloc for 2 years, and it survived several power failures without issue so I don't know if the concerns were warranted.
– Johnny
Aug 29 at 20:17










6 Answers
6






active

oldest

votes

















up vote
72
down vote



accepted










Pros:



  1. None

Cons:



  1. It interrupts the flow of the Emergency Power Off (EPO) in the datacenter. If there is a life or death emergency in a datacenter, that EPO might be triggered to save someone's life. If your rack has its own UPS, it will violate that EPO order.


  2. You will not get extended runtime. Chances are as soon as your upstream UPS switches into battery mode, your UPS will detect the change in sine wave and drop into backup mode as well.


  3. You'll violate your warranty and potentially your datacenter's UPS warranty. UPSs are warrantied to be installed in very specific scenarios and power sources. Your UPS-on-UPS is not going to be a supported configuration.


  4. (from rexkogitans) You have to care about your UPS while there is a staff caring for a UPS that may be provided to you nonetheless. So it adds administrating a UPS to your work really unnecessarily.






share|improve this answer


















  • 6




    Can you elaborate on how this could create or contribute to a life-threatening situation?
    – R..
    Aug 27 at 16:09






  • 25




    @R.. The most obvious to me is if a faulty power supply cause an employee to get electrical shock. If a colleague notice this soon enough and cut power to the rack it may prevent this being fatal. But if there is an unauthorized UPS that could mean the electrical shock is not mitigated by powering off the rack. The other possibility is in the event of a cooling failure it may be necessary to cut power to prevent fire and/or damage to equipment. If there were several unauthorized UPS that wouldn't be an effective mitigation.
    – kasperd
    Aug 27 at 16:21






  • 8




    @R.. yeah pretty much was kasperd said. If the datacenter has a serious enough issue that they need to hit the EPO button, then they need everything off. If your rack is still there consuming 30A of 240v power after they think everything is off then you can contribute to injury.
    – Mark Henderson♦
    Aug 27 at 16:47






  • 2




    @kasperd: Ah. I always use low-voltage DC-DC UPS's, so I wasn't thinking about the possibility of having mains-level output from a UPS.
    – R..
    Aug 27 at 17:18






  • 2




    @R.. A low voltage does address some of the concerns. Other concerns can be addressed by using a battery which only the capacity you need for a clean shutdown and not a big battery that can keep your server running for many minutes and maybe even an hour. And more concerns can be addressed by discussing your plans with the datacenter before you implement them.
    – kasperd
    Aug 27 at 17:41

















up vote
32
down vote













Apart from low-probability scenarios, the single most important reason an unnecessary UPS really cheeses people off is that a year or two from now, it will start beeping.



An UPS needs regular battery replacements, and it usually tells about it by making a really annoying beeping noise that goes on forever. In a locked-up rack. Right next to the other rack you are trying to get some work done on. And it will keep making that noise for days (or months), because whoever installed it and didn't maintain it, also couldn't be bothered to configure any remote alerts on it.



And adding insult to injury, all this happened, because someone wouldn't trust the much better UPS system already in place. Yes, use an UPS when you have to place your rack in a utility closet of an 18th century farm house. But don't do it, when you have way more reliable power readily available on the outer side of the UPS.






share|improve this answer



























    up vote
    15
    down vote













    You may need to run your own UPS when your datacenter doesn't quite deserve the name and it does not provide centralised UPS for you and other customers.

    On the other hand, if that is the case there will probably not be a rule preventing you from installing your own though.



    If you only get a couple of units in the top of a cabinet, good luck hoisting your UPS that high and not tipping over the cabinet, those things can be heavy!



    And maybe stating the obvious: an implied consequence when you need to run your own UPS, is that everything that is not connected to it will not be protected. That may include your connectivity and other services the datacenter provides.






    share|improve this answer





























      up vote
      8
      down vote













      Don't forget the Electrical Code. Most have something like NEC 110.3b, "equipment must be used according to its labeling and instructions".*



      That gives the instructions the same force of law as the Code itself.



      If your UPS says "do not feed from a UPS" or if the datacenter's UPS says "do not supply UPS's", then you place the datacenter in dutch with the electrical codes. You don't get written up - they do.




      * Because that is the scope of testing that was done when it was UL listed. This section is partner to 110.2, which requires only approved equipment be used. All this is on the first page of NEC. You can't miss it.






      share|improve this answer




















      • Um, where in the US legal code does it say that I have to follow the label on an electrical device?
        – zymhan
        Aug 28 at 18:24







      • 5




        @zymhan in the electrical codes, which are cast at the state or community level. In the US, nearly every single jurisdiction incorporates NEC by reference. Technically NEC is a "model law", authored by a nonprofit, and offered to any government which wants to make it their actual law, with or without local customization. Most jurisdictions say "we adopt NEC 2014 as law, with the following changes: a b c". Congress ratifies the bill, sends it to the governor, he signs it, and NEC 2014 (as modded) is the law of the land.
        – Harper
        Aug 28 at 18:33











      • @zymhan - It likely doesn't. People have sued (and won) with much less than the explicit letter of the law. Precedent matters almost as much as the law itself.
        – Dan Esparza
        Aug 29 at 11:05










      • If you construct a building, sure you could be criminally liable for violating the code. But no random person is going to be held criminally liable for connecting a UPS in a datacenter. And being sued has nothing to do with criminal law. But this is a computer forum, so that's neither here nor there.
        – zymhan
        Aug 29 at 21:25

















      up vote
      2
      down vote













      Most rack-style UPS units have, according to their label specifications, significantly higher input wattages than the equipment they are used to feed. No matter what alternate calculations or measurements or precautions YOU took, a third party planner or inspector HAS to assume that the power feed to such a unit needs to be dimensioned for what is on the label of that unit.



      Also, while you might say "worst it can do, should it unexpectedly draw all of its rated power, is trip an overcurrent device, which is rated for the ampacity of all wiring behind it" - in a multi-tenant situation, this happening can affect other customer equipment. And every unscheduled reboot or disturbance of customer equipment, even if it is still within SLA tolerances, drastically worsens that customer's satisfaction with the provider.



      TL;DR for next two paragraphs: Corrosive liquids, flammable gasses, electrocution hazards.



      Also, all common battery systems are a chemical hazard - outgassing (lead acid batteries can generate flammable gas if a charger fails in the wrong way), leakage and subsequent corrosion (in the worst case of someone else's equipment. Lead-Acid batteries contain sulfuric acid, which is the very definition of a corrosive chemical!), fire (especially with new-school lithium systems that seem to be entering the market - also, a fire safety system designed to deal with an electrical or battery gas fire might not be designed to deal with a metal fire!)... if you bring in equipment of a brand/model/design and/or in a condition that differs from what the personnel in that datacenter knows well in practice, it will mean an unknown risk and extra training requirements.



      Also, most UPS units can easily form an "IT" type mains on their own by accident - which presents an electrical hazard. This has nothing to do with IT, I am referring to "isole terre", meaning a floating-ground AC mains supply that could cause severe injury without any RCD type device interfering!



      Personnel that is well experienced and trained in both types of hazards with their own choice of equipment could have a hard time dealing with your equipment if there is any incendent - not knowing eg how to shut it down NOW and RELIABLY if there is an electrical accident downstream of the unit, or how to quickly and safely remove a battery that failed catastrophically.






      share|improve this answer



























        up vote
        1
        down vote













        I can think of two things that this might help with, and that is providing you with the ability to network control your own power to nodes for the purpose of on-demand full node shutdown/poweron and power-based fencing for clustering.



        Don't do it, though. If your colo does not offer these features and you need them, go elsewhere with your business.






        share|improve this answer
















        • 7




          Please note that you don't need a fully fledged UPS for remote power control, a switched power distribution unit (PDU) is sufficient (and a lot cheaper per outlet as well)
          – HBruijn♦
          Aug 27 at 15:19










        • If it's an actual server hardware, won't it have power control via the BMC already?
          – grawity
          Aug 27 at 19:04










        • If that is configured, yes. That's a better way of doing things in most cases. In some colos, customers don't have access to the BMC of the machine they're running on. There are a few reasons why you might not have IPMI, but it's generally preferred.
          – Spooler
          Aug 27 at 20:32










        Your Answer







        StackExchange.ready(function()
        var channelOptions =
        tags: "".split(" "),
        id: "2"
        ;
        initTagRenderer("".split(" "), "".split(" "), channelOptions);

        StackExchange.using("externalEditor", function()
        // Have to fire editor after snippets, if snippets enabled
        if (StackExchange.settings.snippets.snippetsEnabled)
        StackExchange.using("snippets", function()
        createEditor();
        );

        else
        createEditor();

        );

        function createEditor()
        StackExchange.prepareEditor(
        heartbeatType: 'answer',
        convertImagesToLinks: true,
        noModals: false,
        showLowRepImageUploadWarning: true,
        reputationToPostImages: 10,
        bindNavPrevention: true,
        postfix: "",
        onDemand: true,
        discardSelector: ".discard-answer"
        ,immediatelyShowMarkdownHelp:true
        );



        );













         

        draft saved


        draft discarded


















        StackExchange.ready(
        function ()
        StackExchange.openid.initPostLogin('.new-post-login', 'https%3a%2f%2fserverfault.com%2fquestions%2f928159%2fwhat-are-the-pros-and-cons-of-having-your-own-ups-attached-to-your-own-server-ho%23new-answer', 'question_page');

        );

        Post as a guest






























        6 Answers
        6






        active

        oldest

        votes








        6 Answers
        6






        active

        oldest

        votes









        active

        oldest

        votes






        active

        oldest

        votes








        up vote
        72
        down vote



        accepted










        Pros:



        1. None

        Cons:



        1. It interrupts the flow of the Emergency Power Off (EPO) in the datacenter. If there is a life or death emergency in a datacenter, that EPO might be triggered to save someone's life. If your rack has its own UPS, it will violate that EPO order.


        2. You will not get extended runtime. Chances are as soon as your upstream UPS switches into battery mode, your UPS will detect the change in sine wave and drop into backup mode as well.


        3. You'll violate your warranty and potentially your datacenter's UPS warranty. UPSs are warrantied to be installed in very specific scenarios and power sources. Your UPS-on-UPS is not going to be a supported configuration.


        4. (from rexkogitans) You have to care about your UPS while there is a staff caring for a UPS that may be provided to you nonetheless. So it adds administrating a UPS to your work really unnecessarily.






        share|improve this answer


















        • 6




          Can you elaborate on how this could create or contribute to a life-threatening situation?
          – R..
          Aug 27 at 16:09






        • 25




          @R.. The most obvious to me is if a faulty power supply cause an employee to get electrical shock. If a colleague notice this soon enough and cut power to the rack it may prevent this being fatal. But if there is an unauthorized UPS that could mean the electrical shock is not mitigated by powering off the rack. The other possibility is in the event of a cooling failure it may be necessary to cut power to prevent fire and/or damage to equipment. If there were several unauthorized UPS that wouldn't be an effective mitigation.
          – kasperd
          Aug 27 at 16:21






        • 8




          @R.. yeah pretty much was kasperd said. If the datacenter has a serious enough issue that they need to hit the EPO button, then they need everything off. If your rack is still there consuming 30A of 240v power after they think everything is off then you can contribute to injury.
          – Mark Henderson♦
          Aug 27 at 16:47






        • 2




          @kasperd: Ah. I always use low-voltage DC-DC UPS's, so I wasn't thinking about the possibility of having mains-level output from a UPS.
          – R..
          Aug 27 at 17:18






        • 2




          @R.. A low voltage does address some of the concerns. Other concerns can be addressed by using a battery which only the capacity you need for a clean shutdown and not a big battery that can keep your server running for many minutes and maybe even an hour. And more concerns can be addressed by discussing your plans with the datacenter before you implement them.
          – kasperd
          Aug 27 at 17:41














        up vote
        72
        down vote



        accepted










        Pros:



        1. None

        Cons:



        1. It interrupts the flow of the Emergency Power Off (EPO) in the datacenter. If there is a life or death emergency in a datacenter, that EPO might be triggered to save someone's life. If your rack has its own UPS, it will violate that EPO order.


        2. You will not get extended runtime. Chances are as soon as your upstream UPS switches into battery mode, your UPS will detect the change in sine wave and drop into backup mode as well.


        3. You'll violate your warranty and potentially your datacenter's UPS warranty. UPSs are warrantied to be installed in very specific scenarios and power sources. Your UPS-on-UPS is not going to be a supported configuration.


        4. (from rexkogitans) You have to care about your UPS while there is a staff caring for a UPS that may be provided to you nonetheless. So it adds administrating a UPS to your work really unnecessarily.






        share|improve this answer


















        • 6




          Can you elaborate on how this could create or contribute to a life-threatening situation?
          – R..
          Aug 27 at 16:09






        • 25




          @R.. The most obvious to me is if a faulty power supply cause an employee to get electrical shock. If a colleague notice this soon enough and cut power to the rack it may prevent this being fatal. But if there is an unauthorized UPS that could mean the electrical shock is not mitigated by powering off the rack. The other possibility is in the event of a cooling failure it may be necessary to cut power to prevent fire and/or damage to equipment. If there were several unauthorized UPS that wouldn't be an effective mitigation.
          – kasperd
          Aug 27 at 16:21






        • 8




          @R.. yeah pretty much was kasperd said. If the datacenter has a serious enough issue that they need to hit the EPO button, then they need everything off. If your rack is still there consuming 30A of 240v power after they think everything is off then you can contribute to injury.
          – Mark Henderson♦
          Aug 27 at 16:47






        • 2




          @kasperd: Ah. I always use low-voltage DC-DC UPS's, so I wasn't thinking about the possibility of having mains-level output from a UPS.
          – R..
          Aug 27 at 17:18






        • 2




          @R.. A low voltage does address some of the concerns. Other concerns can be addressed by using a battery which only the capacity you need for a clean shutdown and not a big battery that can keep your server running for many minutes and maybe even an hour. And more concerns can be addressed by discussing your plans with the datacenter before you implement them.
          – kasperd
          Aug 27 at 17:41












        up vote
        72
        down vote



        accepted







        up vote
        72
        down vote



        accepted






        Pros:



        1. None

        Cons:



        1. It interrupts the flow of the Emergency Power Off (EPO) in the datacenter. If there is a life or death emergency in a datacenter, that EPO might be triggered to save someone's life. If your rack has its own UPS, it will violate that EPO order.


        2. You will not get extended runtime. Chances are as soon as your upstream UPS switches into battery mode, your UPS will detect the change in sine wave and drop into backup mode as well.


        3. You'll violate your warranty and potentially your datacenter's UPS warranty. UPSs are warrantied to be installed in very specific scenarios and power sources. Your UPS-on-UPS is not going to be a supported configuration.


        4. (from rexkogitans) You have to care about your UPS while there is a staff caring for a UPS that may be provided to you nonetheless. So it adds administrating a UPS to your work really unnecessarily.






        share|improve this answer














        Pros:



        1. None

        Cons:



        1. It interrupts the flow of the Emergency Power Off (EPO) in the datacenter. If there is a life or death emergency in a datacenter, that EPO might be triggered to save someone's life. If your rack has its own UPS, it will violate that EPO order.


        2. You will not get extended runtime. Chances are as soon as your upstream UPS switches into battery mode, your UPS will detect the change in sine wave and drop into backup mode as well.


        3. You'll violate your warranty and potentially your datacenter's UPS warranty. UPSs are warrantied to be installed in very specific scenarios and power sources. Your UPS-on-UPS is not going to be a supported configuration.


        4. (from rexkogitans) You have to care about your UPS while there is a staff caring for a UPS that may be provided to you nonetheless. So it adds administrating a UPS to your work really unnecessarily.







        share|improve this answer














        share|improve this answer



        share|improve this answer








        edited Aug 30 at 16:57

























        answered Aug 27 at 13:31









        Mark Henderson♦

        59.9k28157238




        59.9k28157238







        • 6




          Can you elaborate on how this could create or contribute to a life-threatening situation?
          – R..
          Aug 27 at 16:09






        • 25




          @R.. The most obvious to me is if a faulty power supply cause an employee to get electrical shock. If a colleague notice this soon enough and cut power to the rack it may prevent this being fatal. But if there is an unauthorized UPS that could mean the electrical shock is not mitigated by powering off the rack. The other possibility is in the event of a cooling failure it may be necessary to cut power to prevent fire and/or damage to equipment. If there were several unauthorized UPS that wouldn't be an effective mitigation.
          – kasperd
          Aug 27 at 16:21






        • 8




          @R.. yeah pretty much was kasperd said. If the datacenter has a serious enough issue that they need to hit the EPO button, then they need everything off. If your rack is still there consuming 30A of 240v power after they think everything is off then you can contribute to injury.
          – Mark Henderson♦
          Aug 27 at 16:47






        • 2




          @kasperd: Ah. I always use low-voltage DC-DC UPS's, so I wasn't thinking about the possibility of having mains-level output from a UPS.
          – R..
          Aug 27 at 17:18






        • 2




          @R.. A low voltage does address some of the concerns. Other concerns can be addressed by using a battery which only the capacity you need for a clean shutdown and not a big battery that can keep your server running for many minutes and maybe even an hour. And more concerns can be addressed by discussing your plans with the datacenter before you implement them.
          – kasperd
          Aug 27 at 17:41












        • 6




          Can you elaborate on how this could create or contribute to a life-threatening situation?
          – R..
          Aug 27 at 16:09






        • 25




          @R.. The most obvious to me is if a faulty power supply cause an employee to get electrical shock. If a colleague notice this soon enough and cut power to the rack it may prevent this being fatal. But if there is an unauthorized UPS that could mean the electrical shock is not mitigated by powering off the rack. The other possibility is in the event of a cooling failure it may be necessary to cut power to prevent fire and/or damage to equipment. If there were several unauthorized UPS that wouldn't be an effective mitigation.
          – kasperd
          Aug 27 at 16:21






        • 8




          @R.. yeah pretty much was kasperd said. If the datacenter has a serious enough issue that they need to hit the EPO button, then they need everything off. If your rack is still there consuming 30A of 240v power after they think everything is off then you can contribute to injury.
          – Mark Henderson♦
          Aug 27 at 16:47






        • 2




          @kasperd: Ah. I always use low-voltage DC-DC UPS's, so I wasn't thinking about the possibility of having mains-level output from a UPS.
          – R..
          Aug 27 at 17:18






        • 2




          @R.. A low voltage does address some of the concerns. Other concerns can be addressed by using a battery which only the capacity you need for a clean shutdown and not a big battery that can keep your server running for many minutes and maybe even an hour. And more concerns can be addressed by discussing your plans with the datacenter before you implement them.
          – kasperd
          Aug 27 at 17:41







        6




        6




        Can you elaborate on how this could create or contribute to a life-threatening situation?
        – R..
        Aug 27 at 16:09




        Can you elaborate on how this could create or contribute to a life-threatening situation?
        – R..
        Aug 27 at 16:09




        25




        25




        @R.. The most obvious to me is if a faulty power supply cause an employee to get electrical shock. If a colleague notice this soon enough and cut power to the rack it may prevent this being fatal. But if there is an unauthorized UPS that could mean the electrical shock is not mitigated by powering off the rack. The other possibility is in the event of a cooling failure it may be necessary to cut power to prevent fire and/or damage to equipment. If there were several unauthorized UPS that wouldn't be an effective mitigation.
        – kasperd
        Aug 27 at 16:21




        @R.. The most obvious to me is if a faulty power supply cause an employee to get electrical shock. If a colleague notice this soon enough and cut power to the rack it may prevent this being fatal. But if there is an unauthorized UPS that could mean the electrical shock is not mitigated by powering off the rack. The other possibility is in the event of a cooling failure it may be necessary to cut power to prevent fire and/or damage to equipment. If there were several unauthorized UPS that wouldn't be an effective mitigation.
        – kasperd
        Aug 27 at 16:21




        8




        8




        @R.. yeah pretty much was kasperd said. If the datacenter has a serious enough issue that they need to hit the EPO button, then they need everything off. If your rack is still there consuming 30A of 240v power after they think everything is off then you can contribute to injury.
        – Mark Henderson♦
        Aug 27 at 16:47




        @R.. yeah pretty much was kasperd said. If the datacenter has a serious enough issue that they need to hit the EPO button, then they need everything off. If your rack is still there consuming 30A of 240v power after they think everything is off then you can contribute to injury.
        – Mark Henderson♦
        Aug 27 at 16:47




        2




        2




        @kasperd: Ah. I always use low-voltage DC-DC UPS's, so I wasn't thinking about the possibility of having mains-level output from a UPS.
        – R..
        Aug 27 at 17:18




        @kasperd: Ah. I always use low-voltage DC-DC UPS's, so I wasn't thinking about the possibility of having mains-level output from a UPS.
        – R..
        Aug 27 at 17:18




        2




        2




        @R.. A low voltage does address some of the concerns. Other concerns can be addressed by using a battery which only the capacity you need for a clean shutdown and not a big battery that can keep your server running for many minutes and maybe even an hour. And more concerns can be addressed by discussing your plans with the datacenter before you implement them.
        – kasperd
        Aug 27 at 17:41




        @R.. A low voltage does address some of the concerns. Other concerns can be addressed by using a battery which only the capacity you need for a clean shutdown and not a big battery that can keep your server running for many minutes and maybe even an hour. And more concerns can be addressed by discussing your plans with the datacenter before you implement them.
        – kasperd
        Aug 27 at 17:41












        up vote
        32
        down vote













        Apart from low-probability scenarios, the single most important reason an unnecessary UPS really cheeses people off is that a year or two from now, it will start beeping.



        An UPS needs regular battery replacements, and it usually tells about it by making a really annoying beeping noise that goes on forever. In a locked-up rack. Right next to the other rack you are trying to get some work done on. And it will keep making that noise for days (or months), because whoever installed it and didn't maintain it, also couldn't be bothered to configure any remote alerts on it.



        And adding insult to injury, all this happened, because someone wouldn't trust the much better UPS system already in place. Yes, use an UPS when you have to place your rack in a utility closet of an 18th century farm house. But don't do it, when you have way more reliable power readily available on the outer side of the UPS.






        share|improve this answer
























          up vote
          32
          down vote













          Apart from low-probability scenarios, the single most important reason an unnecessary UPS really cheeses people off is that a year or two from now, it will start beeping.



          An UPS needs regular battery replacements, and it usually tells about it by making a really annoying beeping noise that goes on forever. In a locked-up rack. Right next to the other rack you are trying to get some work done on. And it will keep making that noise for days (or months), because whoever installed it and didn't maintain it, also couldn't be bothered to configure any remote alerts on it.



          And adding insult to injury, all this happened, because someone wouldn't trust the much better UPS system already in place. Yes, use an UPS when you have to place your rack in a utility closet of an 18th century farm house. But don't do it, when you have way more reliable power readily available on the outer side of the UPS.






          share|improve this answer






















            up vote
            32
            down vote










            up vote
            32
            down vote









            Apart from low-probability scenarios, the single most important reason an unnecessary UPS really cheeses people off is that a year or two from now, it will start beeping.



            An UPS needs regular battery replacements, and it usually tells about it by making a really annoying beeping noise that goes on forever. In a locked-up rack. Right next to the other rack you are trying to get some work done on. And it will keep making that noise for days (or months), because whoever installed it and didn't maintain it, also couldn't be bothered to configure any remote alerts on it.



            And adding insult to injury, all this happened, because someone wouldn't trust the much better UPS system already in place. Yes, use an UPS when you have to place your rack in a utility closet of an 18th century farm house. But don't do it, when you have way more reliable power readily available on the outer side of the UPS.






            share|improve this answer












            Apart from low-probability scenarios, the single most important reason an unnecessary UPS really cheeses people off is that a year or two from now, it will start beeping.



            An UPS needs regular battery replacements, and it usually tells about it by making a really annoying beeping noise that goes on forever. In a locked-up rack. Right next to the other rack you are trying to get some work done on. And it will keep making that noise for days (or months), because whoever installed it and didn't maintain it, also couldn't be bothered to configure any remote alerts on it.



            And adding insult to injury, all this happened, because someone wouldn't trust the much better UPS system already in place. Yes, use an UPS when you have to place your rack in a utility closet of an 18th century farm house. But don't do it, when you have way more reliable power readily available on the outer side of the UPS.







            share|improve this answer












            share|improve this answer



            share|improve this answer










            answered Aug 28 at 5:45









            Bass

            44114




            44114




















                up vote
                15
                down vote













                You may need to run your own UPS when your datacenter doesn't quite deserve the name and it does not provide centralised UPS for you and other customers.

                On the other hand, if that is the case there will probably not be a rule preventing you from installing your own though.



                If you only get a couple of units in the top of a cabinet, good luck hoisting your UPS that high and not tipping over the cabinet, those things can be heavy!



                And maybe stating the obvious: an implied consequence when you need to run your own UPS, is that everything that is not connected to it will not be protected. That may include your connectivity and other services the datacenter provides.






                share|improve this answer


























                  up vote
                  15
                  down vote













                  You may need to run your own UPS when your datacenter doesn't quite deserve the name and it does not provide centralised UPS for you and other customers.

                  On the other hand, if that is the case there will probably not be a rule preventing you from installing your own though.



                  If you only get a couple of units in the top of a cabinet, good luck hoisting your UPS that high and not tipping over the cabinet, those things can be heavy!



                  And maybe stating the obvious: an implied consequence when you need to run your own UPS, is that everything that is not connected to it will not be protected. That may include your connectivity and other services the datacenter provides.






                  share|improve this answer
























                    up vote
                    15
                    down vote










                    up vote
                    15
                    down vote









                    You may need to run your own UPS when your datacenter doesn't quite deserve the name and it does not provide centralised UPS for you and other customers.

                    On the other hand, if that is the case there will probably not be a rule preventing you from installing your own though.



                    If you only get a couple of units in the top of a cabinet, good luck hoisting your UPS that high and not tipping over the cabinet, those things can be heavy!



                    And maybe stating the obvious: an implied consequence when you need to run your own UPS, is that everything that is not connected to it will not be protected. That may include your connectivity and other services the datacenter provides.






                    share|improve this answer














                    You may need to run your own UPS when your datacenter doesn't quite deserve the name and it does not provide centralised UPS for you and other customers.

                    On the other hand, if that is the case there will probably not be a rule preventing you from installing your own though.



                    If you only get a couple of units in the top of a cabinet, good luck hoisting your UPS that high and not tipping over the cabinet, those things can be heavy!



                    And maybe stating the obvious: an implied consequence when you need to run your own UPS, is that everything that is not connected to it will not be protected. That may include your connectivity and other services the datacenter provides.







                    share|improve this answer














                    share|improve this answer



                    share|improve this answer








                    edited Aug 27 at 14:35

























                    answered Aug 27 at 14:14









                    HBruijn♦

                    49.7k1079134




                    49.7k1079134




















                        up vote
                        8
                        down vote













                        Don't forget the Electrical Code. Most have something like NEC 110.3b, "equipment must be used according to its labeling and instructions".*



                        That gives the instructions the same force of law as the Code itself.



                        If your UPS says "do not feed from a UPS" or if the datacenter's UPS says "do not supply UPS's", then you place the datacenter in dutch with the electrical codes. You don't get written up - they do.




                        * Because that is the scope of testing that was done when it was UL listed. This section is partner to 110.2, which requires only approved equipment be used. All this is on the first page of NEC. You can't miss it.






                        share|improve this answer




















                        • Um, where in the US legal code does it say that I have to follow the label on an electrical device?
                          – zymhan
                          Aug 28 at 18:24







                        • 5




                          @zymhan in the electrical codes, which are cast at the state or community level. In the US, nearly every single jurisdiction incorporates NEC by reference. Technically NEC is a "model law", authored by a nonprofit, and offered to any government which wants to make it their actual law, with or without local customization. Most jurisdictions say "we adopt NEC 2014 as law, with the following changes: a b c". Congress ratifies the bill, sends it to the governor, he signs it, and NEC 2014 (as modded) is the law of the land.
                          – Harper
                          Aug 28 at 18:33











                        • @zymhan - It likely doesn't. People have sued (and won) with much less than the explicit letter of the law. Precedent matters almost as much as the law itself.
                          – Dan Esparza
                          Aug 29 at 11:05










                        • If you construct a building, sure you could be criminally liable for violating the code. But no random person is going to be held criminally liable for connecting a UPS in a datacenter. And being sued has nothing to do with criminal law. But this is a computer forum, so that's neither here nor there.
                          – zymhan
                          Aug 29 at 21:25














                        up vote
                        8
                        down vote













                        Don't forget the Electrical Code. Most have something like NEC 110.3b, "equipment must be used according to its labeling and instructions".*



                        That gives the instructions the same force of law as the Code itself.



                        If your UPS says "do not feed from a UPS" or if the datacenter's UPS says "do not supply UPS's", then you place the datacenter in dutch with the electrical codes. You don't get written up - they do.




                        * Because that is the scope of testing that was done when it was UL listed. This section is partner to 110.2, which requires only approved equipment be used. All this is on the first page of NEC. You can't miss it.






                        share|improve this answer




















                        • Um, where in the US legal code does it say that I have to follow the label on an electrical device?
                          – zymhan
                          Aug 28 at 18:24







                        • 5




                          @zymhan in the electrical codes, which are cast at the state or community level. In the US, nearly every single jurisdiction incorporates NEC by reference. Technically NEC is a "model law", authored by a nonprofit, and offered to any government which wants to make it their actual law, with or without local customization. Most jurisdictions say "we adopt NEC 2014 as law, with the following changes: a b c". Congress ratifies the bill, sends it to the governor, he signs it, and NEC 2014 (as modded) is the law of the land.
                          – Harper
                          Aug 28 at 18:33











                        • @zymhan - It likely doesn't. People have sued (and won) with much less than the explicit letter of the law. Precedent matters almost as much as the law itself.
                          – Dan Esparza
                          Aug 29 at 11:05










                        • If you construct a building, sure you could be criminally liable for violating the code. But no random person is going to be held criminally liable for connecting a UPS in a datacenter. And being sued has nothing to do with criminal law. But this is a computer forum, so that's neither here nor there.
                          – zymhan
                          Aug 29 at 21:25












                        up vote
                        8
                        down vote










                        up vote
                        8
                        down vote









                        Don't forget the Electrical Code. Most have something like NEC 110.3b, "equipment must be used according to its labeling and instructions".*



                        That gives the instructions the same force of law as the Code itself.



                        If your UPS says "do not feed from a UPS" or if the datacenter's UPS says "do not supply UPS's", then you place the datacenter in dutch with the electrical codes. You don't get written up - they do.




                        * Because that is the scope of testing that was done when it was UL listed. This section is partner to 110.2, which requires only approved equipment be used. All this is on the first page of NEC. You can't miss it.






                        share|improve this answer












                        Don't forget the Electrical Code. Most have something like NEC 110.3b, "equipment must be used according to its labeling and instructions".*



                        That gives the instructions the same force of law as the Code itself.



                        If your UPS says "do not feed from a UPS" or if the datacenter's UPS says "do not supply UPS's", then you place the datacenter in dutch with the electrical codes. You don't get written up - they do.




                        * Because that is the scope of testing that was done when it was UL listed. This section is partner to 110.2, which requires only approved equipment be used. All this is on the first page of NEC. You can't miss it.







                        share|improve this answer












                        share|improve this answer



                        share|improve this answer










                        answered Aug 28 at 10:12









                        Harper

                        1811




                        1811











                        • Um, where in the US legal code does it say that I have to follow the label on an electrical device?
                          – zymhan
                          Aug 28 at 18:24







                        • 5




                          @zymhan in the electrical codes, which are cast at the state or community level. In the US, nearly every single jurisdiction incorporates NEC by reference. Technically NEC is a "model law", authored by a nonprofit, and offered to any government which wants to make it their actual law, with or without local customization. Most jurisdictions say "we adopt NEC 2014 as law, with the following changes: a b c". Congress ratifies the bill, sends it to the governor, he signs it, and NEC 2014 (as modded) is the law of the land.
                          – Harper
                          Aug 28 at 18:33











                        • @zymhan - It likely doesn't. People have sued (and won) with much less than the explicit letter of the law. Precedent matters almost as much as the law itself.
                          – Dan Esparza
                          Aug 29 at 11:05










                        • If you construct a building, sure you could be criminally liable for violating the code. But no random person is going to be held criminally liable for connecting a UPS in a datacenter. And being sued has nothing to do with criminal law. But this is a computer forum, so that's neither here nor there.
                          – zymhan
                          Aug 29 at 21:25
















                        • Um, where in the US legal code does it say that I have to follow the label on an electrical device?
                          – zymhan
                          Aug 28 at 18:24







                        • 5




                          @zymhan in the electrical codes, which are cast at the state or community level. In the US, nearly every single jurisdiction incorporates NEC by reference. Technically NEC is a "model law", authored by a nonprofit, and offered to any government which wants to make it their actual law, with or without local customization. Most jurisdictions say "we adopt NEC 2014 as law, with the following changes: a b c". Congress ratifies the bill, sends it to the governor, he signs it, and NEC 2014 (as modded) is the law of the land.
                          – Harper
                          Aug 28 at 18:33











                        • @zymhan - It likely doesn't. People have sued (and won) with much less than the explicit letter of the law. Precedent matters almost as much as the law itself.
                          – Dan Esparza
                          Aug 29 at 11:05










                        • If you construct a building, sure you could be criminally liable for violating the code. But no random person is going to be held criminally liable for connecting a UPS in a datacenter. And being sued has nothing to do with criminal law. But this is a computer forum, so that's neither here nor there.
                          – zymhan
                          Aug 29 at 21:25















                        Um, where in the US legal code does it say that I have to follow the label on an electrical device?
                        – zymhan
                        Aug 28 at 18:24





                        Um, where in the US legal code does it say that I have to follow the label on an electrical device?
                        – zymhan
                        Aug 28 at 18:24





                        5




                        5




                        @zymhan in the electrical codes, which are cast at the state or community level. In the US, nearly every single jurisdiction incorporates NEC by reference. Technically NEC is a "model law", authored by a nonprofit, and offered to any government which wants to make it their actual law, with or without local customization. Most jurisdictions say "we adopt NEC 2014 as law, with the following changes: a b c". Congress ratifies the bill, sends it to the governor, he signs it, and NEC 2014 (as modded) is the law of the land.
                        – Harper
                        Aug 28 at 18:33





                        @zymhan in the electrical codes, which are cast at the state or community level. In the US, nearly every single jurisdiction incorporates NEC by reference. Technically NEC is a "model law", authored by a nonprofit, and offered to any government which wants to make it their actual law, with or without local customization. Most jurisdictions say "we adopt NEC 2014 as law, with the following changes: a b c". Congress ratifies the bill, sends it to the governor, he signs it, and NEC 2014 (as modded) is the law of the land.
                        – Harper
                        Aug 28 at 18:33













                        @zymhan - It likely doesn't. People have sued (and won) with much less than the explicit letter of the law. Precedent matters almost as much as the law itself.
                        – Dan Esparza
                        Aug 29 at 11:05




                        @zymhan - It likely doesn't. People have sued (and won) with much less than the explicit letter of the law. Precedent matters almost as much as the law itself.
                        – Dan Esparza
                        Aug 29 at 11:05












                        If you construct a building, sure you could be criminally liable for violating the code. But no random person is going to be held criminally liable for connecting a UPS in a datacenter. And being sued has nothing to do with criminal law. But this is a computer forum, so that's neither here nor there.
                        – zymhan
                        Aug 29 at 21:25




                        If you construct a building, sure you could be criminally liable for violating the code. But no random person is going to be held criminally liable for connecting a UPS in a datacenter. And being sued has nothing to do with criminal law. But this is a computer forum, so that's neither here nor there.
                        – zymhan
                        Aug 29 at 21:25










                        up vote
                        2
                        down vote













                        Most rack-style UPS units have, according to their label specifications, significantly higher input wattages than the equipment they are used to feed. No matter what alternate calculations or measurements or precautions YOU took, a third party planner or inspector HAS to assume that the power feed to such a unit needs to be dimensioned for what is on the label of that unit.



                        Also, while you might say "worst it can do, should it unexpectedly draw all of its rated power, is trip an overcurrent device, which is rated for the ampacity of all wiring behind it" - in a multi-tenant situation, this happening can affect other customer equipment. And every unscheduled reboot or disturbance of customer equipment, even if it is still within SLA tolerances, drastically worsens that customer's satisfaction with the provider.



                        TL;DR for next two paragraphs: Corrosive liquids, flammable gasses, electrocution hazards.



                        Also, all common battery systems are a chemical hazard - outgassing (lead acid batteries can generate flammable gas if a charger fails in the wrong way), leakage and subsequent corrosion (in the worst case of someone else's equipment. Lead-Acid batteries contain sulfuric acid, which is the very definition of a corrosive chemical!), fire (especially with new-school lithium systems that seem to be entering the market - also, a fire safety system designed to deal with an electrical or battery gas fire might not be designed to deal with a metal fire!)... if you bring in equipment of a brand/model/design and/or in a condition that differs from what the personnel in that datacenter knows well in practice, it will mean an unknown risk and extra training requirements.



                        Also, most UPS units can easily form an "IT" type mains on their own by accident - which presents an electrical hazard. This has nothing to do with IT, I am referring to "isole terre", meaning a floating-ground AC mains supply that could cause severe injury without any RCD type device interfering!



                        Personnel that is well experienced and trained in both types of hazards with their own choice of equipment could have a hard time dealing with your equipment if there is any incendent - not knowing eg how to shut it down NOW and RELIABLY if there is an electrical accident downstream of the unit, or how to quickly and safely remove a battery that failed catastrophically.






                        share|improve this answer
























                          up vote
                          2
                          down vote













                          Most rack-style UPS units have, according to their label specifications, significantly higher input wattages than the equipment they are used to feed. No matter what alternate calculations or measurements or precautions YOU took, a third party planner or inspector HAS to assume that the power feed to such a unit needs to be dimensioned for what is on the label of that unit.



                          Also, while you might say "worst it can do, should it unexpectedly draw all of its rated power, is trip an overcurrent device, which is rated for the ampacity of all wiring behind it" - in a multi-tenant situation, this happening can affect other customer equipment. And every unscheduled reboot or disturbance of customer equipment, even if it is still within SLA tolerances, drastically worsens that customer's satisfaction with the provider.



                          TL;DR for next two paragraphs: Corrosive liquids, flammable gasses, electrocution hazards.



                          Also, all common battery systems are a chemical hazard - outgassing (lead acid batteries can generate flammable gas if a charger fails in the wrong way), leakage and subsequent corrosion (in the worst case of someone else's equipment. Lead-Acid batteries contain sulfuric acid, which is the very definition of a corrosive chemical!), fire (especially with new-school lithium systems that seem to be entering the market - also, a fire safety system designed to deal with an electrical or battery gas fire might not be designed to deal with a metal fire!)... if you bring in equipment of a brand/model/design and/or in a condition that differs from what the personnel in that datacenter knows well in practice, it will mean an unknown risk and extra training requirements.



                          Also, most UPS units can easily form an "IT" type mains on their own by accident - which presents an electrical hazard. This has nothing to do with IT, I am referring to "isole terre", meaning a floating-ground AC mains supply that could cause severe injury without any RCD type device interfering!



                          Personnel that is well experienced and trained in both types of hazards with their own choice of equipment could have a hard time dealing with your equipment if there is any incendent - not knowing eg how to shut it down NOW and RELIABLY if there is an electrical accident downstream of the unit, or how to quickly and safely remove a battery that failed catastrophically.






                          share|improve this answer






















                            up vote
                            2
                            down vote










                            up vote
                            2
                            down vote









                            Most rack-style UPS units have, according to their label specifications, significantly higher input wattages than the equipment they are used to feed. No matter what alternate calculations or measurements or precautions YOU took, a third party planner or inspector HAS to assume that the power feed to such a unit needs to be dimensioned for what is on the label of that unit.



                            Also, while you might say "worst it can do, should it unexpectedly draw all of its rated power, is trip an overcurrent device, which is rated for the ampacity of all wiring behind it" - in a multi-tenant situation, this happening can affect other customer equipment. And every unscheduled reboot or disturbance of customer equipment, even if it is still within SLA tolerances, drastically worsens that customer's satisfaction with the provider.



                            TL;DR for next two paragraphs: Corrosive liquids, flammable gasses, electrocution hazards.



                            Also, all common battery systems are a chemical hazard - outgassing (lead acid batteries can generate flammable gas if a charger fails in the wrong way), leakage and subsequent corrosion (in the worst case of someone else's equipment. Lead-Acid batteries contain sulfuric acid, which is the very definition of a corrosive chemical!), fire (especially with new-school lithium systems that seem to be entering the market - also, a fire safety system designed to deal with an electrical or battery gas fire might not be designed to deal with a metal fire!)... if you bring in equipment of a brand/model/design and/or in a condition that differs from what the personnel in that datacenter knows well in practice, it will mean an unknown risk and extra training requirements.



                            Also, most UPS units can easily form an "IT" type mains on their own by accident - which presents an electrical hazard. This has nothing to do with IT, I am referring to "isole terre", meaning a floating-ground AC mains supply that could cause severe injury without any RCD type device interfering!



                            Personnel that is well experienced and trained in both types of hazards with their own choice of equipment could have a hard time dealing with your equipment if there is any incendent - not knowing eg how to shut it down NOW and RELIABLY if there is an electrical accident downstream of the unit, or how to quickly and safely remove a battery that failed catastrophically.






                            share|improve this answer












                            Most rack-style UPS units have, according to their label specifications, significantly higher input wattages than the equipment they are used to feed. No matter what alternate calculations or measurements or precautions YOU took, a third party planner or inspector HAS to assume that the power feed to such a unit needs to be dimensioned for what is on the label of that unit.



                            Also, while you might say "worst it can do, should it unexpectedly draw all of its rated power, is trip an overcurrent device, which is rated for the ampacity of all wiring behind it" - in a multi-tenant situation, this happening can affect other customer equipment. And every unscheduled reboot or disturbance of customer equipment, even if it is still within SLA tolerances, drastically worsens that customer's satisfaction with the provider.



                            TL;DR for next two paragraphs: Corrosive liquids, flammable gasses, electrocution hazards.



                            Also, all common battery systems are a chemical hazard - outgassing (lead acid batteries can generate flammable gas if a charger fails in the wrong way), leakage and subsequent corrosion (in the worst case of someone else's equipment. Lead-Acid batteries contain sulfuric acid, which is the very definition of a corrosive chemical!), fire (especially with new-school lithium systems that seem to be entering the market - also, a fire safety system designed to deal with an electrical or battery gas fire might not be designed to deal with a metal fire!)... if you bring in equipment of a brand/model/design and/or in a condition that differs from what the personnel in that datacenter knows well in practice, it will mean an unknown risk and extra training requirements.



                            Also, most UPS units can easily form an "IT" type mains on their own by accident - which presents an electrical hazard. This has nothing to do with IT, I am referring to "isole terre", meaning a floating-ground AC mains supply that could cause severe injury without any RCD type device interfering!



                            Personnel that is well experienced and trained in both types of hazards with their own choice of equipment could have a hard time dealing with your equipment if there is any incendent - not knowing eg how to shut it down NOW and RELIABLY if there is an electrical accident downstream of the unit, or how to quickly and safely remove a battery that failed catastrophically.







                            share|improve this answer












                            share|improve this answer



                            share|improve this answer










                            answered Aug 29 at 21:03









                            rackandboneman

                            2,25268




                            2,25268




















                                up vote
                                1
                                down vote













                                I can think of two things that this might help with, and that is providing you with the ability to network control your own power to nodes for the purpose of on-demand full node shutdown/poweron and power-based fencing for clustering.



                                Don't do it, though. If your colo does not offer these features and you need them, go elsewhere with your business.






                                share|improve this answer
















                                • 7




                                  Please note that you don't need a fully fledged UPS for remote power control, a switched power distribution unit (PDU) is sufficient (and a lot cheaper per outlet as well)
                                  – HBruijn♦
                                  Aug 27 at 15:19










                                • If it's an actual server hardware, won't it have power control via the BMC already?
                                  – grawity
                                  Aug 27 at 19:04










                                • If that is configured, yes. That's a better way of doing things in most cases. In some colos, customers don't have access to the BMC of the machine they're running on. There are a few reasons why you might not have IPMI, but it's generally preferred.
                                  – Spooler
                                  Aug 27 at 20:32














                                up vote
                                1
                                down vote













                                I can think of two things that this might help with, and that is providing you with the ability to network control your own power to nodes for the purpose of on-demand full node shutdown/poweron and power-based fencing for clustering.



                                Don't do it, though. If your colo does not offer these features and you need them, go elsewhere with your business.






                                share|improve this answer
















                                • 7




                                  Please note that you don't need a fully fledged UPS for remote power control, a switched power distribution unit (PDU) is sufficient (and a lot cheaper per outlet as well)
                                  – HBruijn♦
                                  Aug 27 at 15:19










                                • If it's an actual server hardware, won't it have power control via the BMC already?
                                  – grawity
                                  Aug 27 at 19:04










                                • If that is configured, yes. That's a better way of doing things in most cases. In some colos, customers don't have access to the BMC of the machine they're running on. There are a few reasons why you might not have IPMI, but it's generally preferred.
                                  – Spooler
                                  Aug 27 at 20:32












                                up vote
                                1
                                down vote










                                up vote
                                1
                                down vote









                                I can think of two things that this might help with, and that is providing you with the ability to network control your own power to nodes for the purpose of on-demand full node shutdown/poweron and power-based fencing for clustering.



                                Don't do it, though. If your colo does not offer these features and you need them, go elsewhere with your business.






                                share|improve this answer












                                I can think of two things that this might help with, and that is providing you with the ability to network control your own power to nodes for the purpose of on-demand full node shutdown/poweron and power-based fencing for clustering.



                                Don't do it, though. If your colo does not offer these features and you need them, go elsewhere with your business.







                                share|improve this answer












                                share|improve this answer



                                share|improve this answer










                                answered Aug 27 at 15:14









                                Spooler

                                5,451925




                                5,451925







                                • 7




                                  Please note that you don't need a fully fledged UPS for remote power control, a switched power distribution unit (PDU) is sufficient (and a lot cheaper per outlet as well)
                                  – HBruijn♦
                                  Aug 27 at 15:19










                                • If it's an actual server hardware, won't it have power control via the BMC already?
                                  – grawity
                                  Aug 27 at 19:04










                                • If that is configured, yes. That's a better way of doing things in most cases. In some colos, customers don't have access to the BMC of the machine they're running on. There are a few reasons why you might not have IPMI, but it's generally preferred.
                                  – Spooler
                                  Aug 27 at 20:32












                                • 7




                                  Please note that you don't need a fully fledged UPS for remote power control, a switched power distribution unit (PDU) is sufficient (and a lot cheaper per outlet as well)
                                  – HBruijn♦
                                  Aug 27 at 15:19










                                • If it's an actual server hardware, won't it have power control via the BMC already?
                                  – grawity
                                  Aug 27 at 19:04










                                • If that is configured, yes. That's a better way of doing things in most cases. In some colos, customers don't have access to the BMC of the machine they're running on. There are a few reasons why you might not have IPMI, but it's generally preferred.
                                  – Spooler
                                  Aug 27 at 20:32







                                7




                                7




                                Please note that you don't need a fully fledged UPS for remote power control, a switched power distribution unit (PDU) is sufficient (and a lot cheaper per outlet as well)
                                – HBruijn♦
                                Aug 27 at 15:19




                                Please note that you don't need a fully fledged UPS for remote power control, a switched power distribution unit (PDU) is sufficient (and a lot cheaper per outlet as well)
                                – HBruijn♦
                                Aug 27 at 15:19












                                If it's an actual server hardware, won't it have power control via the BMC already?
                                – grawity
                                Aug 27 at 19:04




                                If it's an actual server hardware, won't it have power control via the BMC already?
                                – grawity
                                Aug 27 at 19:04












                                If that is configured, yes. That's a better way of doing things in most cases. In some colos, customers don't have access to the BMC of the machine they're running on. There are a few reasons why you might not have IPMI, but it's generally preferred.
                                – Spooler
                                Aug 27 at 20:32




                                If that is configured, yes. That's a better way of doing things in most cases. In some colos, customers don't have access to the BMC of the machine they're running on. There are a few reasons why you might not have IPMI, but it's generally preferred.
                                – Spooler
                                Aug 27 at 20:32

















                                 

                                draft saved


                                draft discarded















































                                 


                                draft saved


                                draft discarded














                                StackExchange.ready(
                                function ()
                                StackExchange.openid.initPostLogin('.new-post-login', 'https%3a%2f%2fserverfault.com%2fquestions%2f928159%2fwhat-are-the-pros-and-cons-of-having-your-own-ups-attached-to-your-own-server-ho%23new-answer', 'question_page');

                                );

                                Post as a guest













































































                                Comments

                                Popular posts from this blog

                                What does second last employer means? [closed]

                                List of Gilmore Girls characters

                                Confectionery